![ECKELMANN Case Controller UA 4 E Series Operating Instruction Download Page 78](http://html2.mh-extra.com/html/eckelmann/case-controller-ua-4-e-series/case-controller-ua-4-e-series_operating-instruction_3927596078.webp)
Firmware V3.13
21.04.2021
78/466
5.8.5.1 Master-slave mode for the synchronisation of the zones of a single contr.
Function description
Master configuration:
With the case controller the internal defrost timer must be active (menu 3-2, parameter
Defrost Timer = INT). This case controller is then designated as the master.
On reaching the defrost end temperature for the respective zone the defrost relay is switched off. Cooling is
only resumed once all the control zones have completed the defrost or the safe defrost time has elapsed.
Example:
Synchronized defrost termination on one controller with two temperature zones.
In standard operation with two temperature zones, the defrost in each zone is terminated dependent on the
defrost termination sensor of the respective zone and immediately switched to cooling. If in contrast, an
operating mode is required where both zones simultaneously switch to cooling following the defrost, then the
master/slave function on DIP switch 3 of coding switch 4 also needs to be set to ON.
Cooling will then not be resumed until defrosting is terminated in both zones. The defrost heater relay is still
operated separately for each zone according to temperature on the defrost termination sensor.
The special features and restrictions for the master now apply, see chapter
synchronisation of the zones of a single contr.
Further details of special features and restrictions are provided in chapter
synchronisation of the zones of a single contr.
.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...