Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 5..20
8 °C
Wait Time XX m
Waiting time setpoint between cooling and defrost
0..15
0 min
Drip Time X m
Waiting time (drip time) setpoint between defrost
and cooling
0..15
0 min
M/S Degiv.Fct. XXX
Configuration of the defrost via CAN bus function.
For details see chapter
.
OFF,
MASTR,
SLAVE
OFF
M/S CAN Adr. XXX
Selection of the controller (1..99) participating in the
defrost via CAN bus which is the master.
“--“, if this controller is itself master
(Parameter M/S Degiv.Fct.. = MASTR)
---, 1..99
--
DS-Function XXX
Configuration of the defrost sequenz function (DS).
For details see chapter
OFF,
MASTR,
SLAVE
OFF
DS-Group XXX
Selection of which group a defrost sequenz of this
controller (1..99) belongs to.
---, 1..99
--
DS-Master XXX
Selection of which controller (1..99) participating in
the defrost sequenz is the master.
“--“, if this controller is itself the master
(Parameter DS-Function = MASTR)
---, 1..99
--
DS-Wait time XXXm
Wait time for the defrost sequenz
0..127
1 min
Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 5..20
8 °C
Wait Time XX m
Waiting time setpoint between cooling and
defrost
0..15
3 min
Drip Time X m
Waiting time (drip time) setpoint between defrost
and cooling
0..15
5 min
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...