![ECKELMANN Case Controller UA 4 E Series Operating Instruction Download Page 241](http://html2.mh-extra.com/html/eckelmann/case-controller-ua-4-e-series/case-controller-ua-4-e-series_operating-instruction_3927596241.webp)
Firmware V3.13
21.04.2021
241/466
•
•
•
Menu 2-1-3 Zone 1T Toggle
COOLING 1A POS: XXXXX
Entry
Default
Setpoint R2.1 XXX °C
Supply air temperature setpoint
--, -40..20
-32 °C
Hysterese R2.1 X K
Supply air temperature hysteresis setpoint; shown
only when on-off control is set (Menu 2-1-1)
1..8
2 K
Setpoint R4.1 XXX °C
Return air temperature setpoint
--, -30..20
-22 °C
Hystersis R4.1 X K
Return air temperature hysteresis setpoint; shown
only when on-off control is set (Menu 2-1-1)
1..8
2 K
Menu 2-1-4 Zone 2T Toggle
COOLING 2A POS: XXXXX
Entry
Default
Setpoint R2.2 XXX °C
Supply air temperature setpoint
--, -40..20
-32 °C
Hystersis R2.2 X K
Supply air temperature hysteresis setpoint; shown
only when on-off control is set (Menu 2-1-2)
1..8
2 K
Setpoint R4.2 XXX °C
Return air temperature setpoint
--, -30..20
-22 °C
Hystersis R4.2 X K
Return air temperature hysteresis setpoint; shown
only when on-off control is set (Menu 2-1-2)
1..8
2 K
Menu 2-2 Defrost
DEFROST POS: XXXXX
1 Zone 1
Move to menu 2-2-1
2 Zone 2
Move to menu 2-2-2; shown only when two-zone operation is set (Menu 6-1)
3 Zone 1T Toggle
Move to menu 2-2-3; not shown when setpoint toggle is deactivated (Menu 3-3)
4 Zone 2T Toggle
Move to menu 2-2-4; shown only when two-zone operation is set (Menu 6-1) and
when
setpoint toggle is not deactivated (Menu 3-3)
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...