![ECKELMANN Case Controller UA 4 E Series Operating Instruction Download Page 195](http://html2.mh-extra.com/html/eckelmann/case-controller-ua-4-e-series/case-controller-ua-4-e-series_operating-instruction_3927596195.webp)
Firmware V3.13
21.04.2021
195/466
•
•
•
Menu 1-6 Frame Heater
MODE XXXXX
Frame Heater XXX
Displays current OFF/ON status of frame heater output Terminal 91/92/93
Run Time XXX %
Displays current frame heater on time
Humidity XXX %
Displays current room air humidity (transmitted via CAN bus from VS pack controller
with fitted humidity sensor)
Room temp. XX °C
Displays current room air temperature (transmitted via CAN bus from VS pack controller
with fitted room air temperature sensor)
Menu 1-7 Cooling Zone 2
COOLING 2 XXXXX
Cooling XXX
Displays current OFF/ON status of cooling
op.deg. Z 2 XX %
Displays current valve opening degree Zone 2
OD med. 24h XX %
Displays mean valve opening degree 2 for past day
Temp. R2.2 XXX °C
Displays current supply air temperature Input Z61/Z62
Setpoint R2.2 XXX °C
Displays supply air temperature setpoint for comparison
Hystersis R2.2 XXX K
Displays supply air temperature hysteresis setpoint; shown only when on-off
control is set (Menu 2-1-2)
Temp. R4.2 XXX °C
Displays current return air temperature Input Z71/Z72
Setpoint R4.2 XXX °C
Displays return air temperature setpoint for comparison
Hystersis R4.2 XXX K
Displays return air temperature hysteresis setpoint; shown only when on-off control
is set (Menu 2-1-2)
SH Z 2 XXX °C
Displays current superheat temperature Zone 2
sup air ctrl XXX
Displays current OFF/ON status of supply or return air control
MOP op. XXX
Displays OFF/ON setpoint of MOP mode
Status hand XXX
Status manual shutdown (ON/OFF)
Menu 1-8 Defrost Zone 2
DEFROST 2 XXXXX
Defrost XXX
Displays current OFF/ON status of defrosting
Temp. R1.2 XXX °C
Displays current evaporator defrost termination temperature Input Z81/Z82
Def. End. Tmp. XXX °C
Displays defrost termination temperature setpoint for comparison
Wait Time XX m
Displays waiting time setpoint
Drip Time XX m
Displays drip time setpoint
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...