Firmware V3.13
21.04.2021
397/466
•
•
•
•
Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
-- °C
Wait Time XX m
Waiting time setpoint between cooling and
defrost
0..15
0 min
Drip Time X m
Waiting time (drip time) setpoint between defrost
and cooling
0..15
0 min
Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
-- °C
Wait Time XX m
Waiting time setpoint between cooling and
defrost
0..15
0 min
Drip Time X m
Waiting time (drip time) setpoint between defrost
and cooling
0..15
0 min
Menu 2-2-3 Zone 1T Toggle
DEFROST 1A POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
-- °C
Wait Time XX m
Waiting time setpoint between cooling and
defrost
0..15
0 min
Drip Time X m
Waiting time (drip time) setpoint between defrost
and cooling
0..15
0 min
Menu 2-2-4 Zone 2T Toggle
DEFROST 2A POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
-- °C
Wait Time XX m
Waiting time setpoint between cooling and
defrost
0..15
0 min
Drip Time X m
Waiting time (drip time) setpoint between defrost
and cooling
0..15
0 min
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...