Firmware V3.13
21.04.2021
323/466
TOG. SETP.POS: XXXXX
Entry
Default
Run Time XXX %
Fixed on time, shown only when mode set to
Fixed OT (Menu 2-5-3)
--, 0..100
100 %
emerg.run time XXX %
On time in loss of humidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-3)
--, 0..100
100 %
enthalp. offs. XXX %
Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-3)
-50..50
0 %