Firmware V3.13
21.04.2021
163/466
Mode of operation „positive”
means that operation of the relay is not inverted:
The relay is energized when the controller activates the function output (e.g. cooling = ON). (This
means that the contact of a normally open relay is closed.)
The relay is not energized when the controller deactivates the function output (e.g. cooling = OFF).
(This means that the contact of a normally open relay is open.)
Mode of operation „inverted”
means that operation of the relay is inverted:
The relay is not energized when the controller activates the function output (e.g. alarm = ON). (This
means that the contact of a normally open relay is open.)
The relay is energized when the controller deactivates the function output (e.g. alarm = OFF). (This
means that the contact of a normally open relay is closed.)
** The function for the frame heater / pane heater can be configured via the parameter „Invert
Output“ (menü 2-5-2 / menu 2-6-2).