Firmware V3.13
21.04.2021
167/466
7.7 Terminal assignment of the CAN bus terminals
For further details about the setting of the CAN bus address see chapter
.
Controller type
Terminal No.
CAN bus
Wire colour
All controllers
1
Shield (SHLD)
Shield
2
CAN-GND
green
3
CAN-LOW
brown
4
CAN-HIGH
white
DANGER
Warning about dangerous electrical voltage!
If mains voltage is connected to the CAN bus
terminals, this will result in the destruction of all components connected to the CAN bus!
ATTENTION
All supply lines from and to the case controller, particularly those of the CAN bus, must be shielded
(cable type: LiYCY)! As a general rule, care should be taken to ensure that signal cables and cables
carrying mains voltage are routed in separate cable channels.
The orange CAN bus LED always flashes when data are being exchanged via the CAN bus with the
system centre / store computer; for details, see chapter
.