Firmware V3.13
21.04.2021
199/466
• Menu 2-1-2 Zone 2
COOLING 2 POS: XXXXX
Entry
Default
Setpoint R2.2 XXX °C
Supply air temperature
setpoint
--, -10..20
Hystersis R2.2 X K
Supply air temperature
hysteresis setpoint;
shown only when on-off
control is set (Menu
2-1-2)
1..8
Setpoint R4.2 XXX °C
Return air temperature
setpoint
--, -10..20
Hystersis R4.2 X K
Return air temperature
hysteresis setpoint;
shown only when on-off
control is set (Menu
2-1-2)
1..8
Superheat XXX K
Superheat setpoint Zone
2
0..20
Min. SH XX K
Minimun superheat
setpoint, below which
cooling relay switches off
Zone 2. I-sum (not I-part)
is set to zero when the
Reset I-Sum parameter is
set to ON.
0..10
Two pos.ctrl XXX
Switch between on-off
control (ON) and
continuous control (OFF)
↑, ↓ (ON/OFF)
MOP-point XXX °C
Starting setpoint for MOP
mode
--, -50..50
Cool. on AOUT XXX%
Kühlung eingeschaltet:
fester Wert 0..10 V für
Analogausgang AO2; nur
sichtbar, wenn von DIP-
Schalter S3 der
Kodierschalter 6 auf ON
steht, siehe Kapitel
Funktionsweise der
Analogausgänge 0..10 V.
80 %
Cool. off AOUT XXX%
Kühlung ausgeschaltet:
fester Wert 0..10 V für
Analogausgang AO2; nur
sichtbar, wenn von DIP-
Schalter S3 der
Kodierschalter 6 auf ON
steht, siehe Kapitel
Funktionsweise der
Analogausgänge 0..10 V.
50 %
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...