Firmware V3.13
21.04.2021
342/466
•
ALARMPRIOS POS: XXXXX
Entry
Default
wrong ctrlr type
Configuration error: Invalid controller type set on DIP
Switch S3. Priority applies to
Wrong Controller Type
alarm
-, 0..99
0
emerg.cut-out SH
Superheat drop below minimum level for duration of
delay time
-, 0..99
0
OD manual
Valve opening degree defined by manual entry.
Priority applies to alarms
VO Manual Zone 1, VO
Manual Zone 2
-, 0..99
0
config:M/S w HG
Configuration error: Simultaneous setting of
parameters for master-slave and discharge gas
defrosting
-, 0..99
2
Check OD
Alarm due to implausible opening degree (see
chapter
Implausible opening position alarm
-, 0..99
0
Extern.Alarm
Alarm for registering external alarms, default text is
“CO2-Alarm”
-, 0..99
0
Menu 6-6 Em.Powersupply (Emergency Power supply)
EM.POW.SUP POS: XXXXX
Entry
Default
Cool.funct.OFF xxx
Functionality of the cooling switched off during
emergency power supply? (Y/N)
↑, ↓ (Y/N)
N
Defr.funct.OFF xxx
Functionality of the defrosting switched off during
emergency power supply? (Y/N)
↑, ↓ (Y/N)
N
Fan funct. OFF xxx
Functionality of the fan switched off during
emergency power supply? (Y/N)
↑, ↓ (Y/N)
N
Frame fct.OFF xxx
Functionality of the frame heater off during
emergency power supply? (Y/N)
↑, ↓ (Y/N)
N
Light fct. OFF xxx
Functionality of the light during emergency power
supply? (Y/N)
↑, ↓ (Y/N)
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...