Firmware V3.13
21.04.2021
263/466
•
•
•
Menu 6-3 Cooling
COOLING POS: XXXXX
Entry
Default
corr.off to XX K
Correction offset for pressure loss in suction line
IMPORTANT
: in stand alone operation must be set to
”--”!
--, 0..20
2 K
Cont Cool Mon. XX m
Continuous run monitoring
--, 0..15
0 min
HG operation XXX
Discharge gas mode
↑, ↓,
(ON/OFF)
OFF
Ret Air Sensor →
Operation with four return air sensors
→ or
↵
Menu 6-3-a
EnablingRel XXX
Switching to “Enable Operation“:
OFF Opening degree is transmitted via the solid state
relay (SSR)
ON The two SSRs are no longer clocking, they are
switched on if the case controller requires
refrigeration, i.e. switched off again if no refrigeration
is required.
↑, ↓,
(ON/OFF)
OFF
Menu 6-3-a return air sensor
RET AIR SENSOR POS: XXXXX
Entry
Default
Temp. R4.3
R4.3 instead R5.1
↑, ↓,
(ON/OFF)
OFF
Temp. R4.4
R4.4 instead R5.2
↑, ↓,
(ON/OFF)
OFF
Weighting R4.3
Weighting between R4.1 and R4.3
0..100
0 %
Weighting R4.4
Weighting between R4.2 and R4.4
0..100
0 %
Menu 6-4 Language
Selection is made according to entry. Checkmark shows current setting.
LANGUAGE POS: XXXXX
Entry
Default
Deutsch D √
√
English GB
Francais F
Espanyol ESP
Finnish FIN
Cesky CZ
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...