Firmware V3.13
21.04.2021
66/466
•
•
•
•
•
5.7.20 Operation with up to four return air sensors - only UA 131 E LS
Only controller type UA 131 E LS
Using the parameter
Temperat. R4.3
or
Temperat. R4.4
(menu 6-3 Return air sensors), the operation of up to
four return air sensors (in one temperature zone) can be enabled, see table.
Number of return air sensors
Temperature zones
UA 401 E CC
UA 400 E CC / UA 410 E AC
Single-zone operation
2
Zone 1: R4.1 / R4.3
2 up to max. 4
Zone 1: R4.1 / R4.3 / R4.2 / R4.4
Two-zone operation
-
2
Zone 1: R4.1 / R4.3
Zone 2: R4.2 / R4.4
Terminal assignment of the analogue inputs for temperature sensors
Configuration
The parameters
Temperat. R4.3
and
Temperat. R4.4
must be set to "
ON
" for this operating mode. Using the
parameter
Wichtung R4.3
, the temperature regulation between the sensors R4.1 and R4.3 and between R4.2
and R4.4 with the parameter
Wichtung R4.4
can be set. With a weighting value of 0%, regulation is carried out
completely according to the original sensor (R4.1 or R4.2), and with a weighting value of 100% completely
according to the respective second sensor (R4.3 or R4.4). Intermediate values result in regulation to the
weighted average of both sensors.
5.8 Defrosting
5.8.1
Types of defrosting – an overview
The following types of defrost are described in the following chapters:
Defrost in general
Discharge gas defrosting (hot gas defrosting)
Master/slave mode – defrost synchronisation via CAN bus
Master/slave mode – defrost synchronisation via wiring
Defrost sequenz (DS) via CAN bus
ATTENTION
In this operating mode the sensors R5.1 and R5.2 for determining the superheat are not required! As
the emergency features are thus omitted (failure of the suction pressure measurement via R5.1 or
R5.2), suitable measures
must
be taken to take into account the absence of the evaporator inlet
sensors R5.1 and R5.2. A suitable measure is the
standalone operation using activated local pressure
ATTENTION
Fire hazard!
On grounds of fire prevention, during the planning of the installation a device for shutting
down the defrost heating in the event of excessive temperature (e.g. ”KLIXON”) must be provided.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...