65
EtherNet/IP On-Board Communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Assembly instance 73
Table 83. Instance 73 (Input) length = 6 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AtReference RefFromNet CtrlFromNet Ready
Running2
Running1
Warning
Faulted
1
Drive state
2
Speed actual (Low Byte), rpm
3
Speed actual (High Byte), rpm
4
Torque actual (Low Byte), Nm
5
Torque actual (High Byte), Nm
See note 1 from
Table 82
on
Page 64
.
Assembly instance 75
Table 84. Instance 75 (Input) length = 6 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AtReference RefFromNet CtrlFromNet Ready
Running2
Running1
Warning
Faulted
1
Drive state
2
Speed actual (Low Byte), rpm
3
Speed actual (High Byte), rpm
4
Process actual (Low Byte), Nm
5
Process actual (High Byte), Nm
See note 1 from
Table 82
on
Page 64
.
Process actual value is same as process reference. This value will be a
0 to 10000 (100.00%) for use with Analog outputs writing,
0 = 0 or 4 mA and 10000 being 20 mAs.
Assembly instance 107
Table 85. Instance 107 (Input) length = 8 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AtReference RefFromNet CtrlFromNet Ready
Running2
Running1
Warning
Faulted
1
Drive State/Processdata Selector Value (if pd selector is used)
2
% Speed actual (Low Byte)
3
% Speed actual (High Byte)
4
Process DataOut1 (Low Byte)
5
Process DataOut1 (High Byte)
6
Process DataOut2 (Low Byte)
7
Process DataOut2 (High Byte)
See note 1 from
Table 82
on
Page 64
.
Speed Actual. This is the actual value from the frequency converter. The value is
between 0 and 10000. In the application, the value is scaled in percentage of frequency
area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
ote:
N
See info on Assembly 101 for varying values in the Process Data Out 1 and
Process Data Out 2 Bytes. See
Appendix B
on default Process Data info.
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...