Assembly instance 127
Table 164. Instance 127 (Input). EIP Drive status length = 20 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
CtrlFromNet
At Zero Speed
At Reference
Alarm/Warning
Faulted
Direction
Running
Ready
1
NA
2
% Speed Actual (Low Byte)
3
% Speed Actual (High Byte)
4 ProcessDataOut1
(LowByte)
5 ProcessDataOut1
(HighByte)
6 ProcessDataOut2
(LowByte)
7 ProcessDataOut2
(HighByte)
8 ProcessDataOut3
(LowByte)
9 ProcessDataOut3
(HighByte)
10 ProcessDataOut4
(LowByte)
11
ProcessDataOut4 (HighByte)
12 ProcessDataOut5
(LowByte)
13
ProcessDataOut5 (HighByte)
14
ProcessDataOut6 (LowByte)
15
ProcessDataOut6 (HighByte)
16
ProcessDataOut7 (LowByte)
17
ProcessDataOut7 (HighByte)
18
ProcessDataOut8 (LowByte)
19 ProcessDataOut8
(HighByte)
This is the actual value from the frequency converter. The value is between 0 and 10000.
In the application, the value is scaled in percentage of frequency area between set
minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
ote:
N
See
Appendix B
for Process Data Value defaults.
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...