162
SmartWire-DT External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Byte
Bit
Designation
Meaning
1
8
Jog 1
Jog with set point value 1
If this bit and byte 1, bit 0 (OnOff) are set to 1 after byte 0, bit 2 (Ctl_PLC); byte 1,
bit 1 (Off2); byte 1, bit 2 (Off3); and byte 1, bit 3 (EN_OP) have been set to 1,the variable frequency drive will start with fixed
frequency 1 in the forward operating direction
9
Jog 2
Reserved – not used as of this writing
10
Ctl_PLC
PLC assumes control (Control by PLC)
0: no control via PLC
1: Control via PLC
If this bit has a value of 1, the PLC will be able to control the variable frequency drive. Before this, the variable frequency drive
will not carry out any commands it receives from the PLC. If the bit has a value of 0, the PLC will not be able to control the variable
frequency drive.
11
I11 (Input 1)
Programmable input 1
Reserved – not used as of this writing
12
I12 (Input 2)
Programmable input 2
Reserved – not used as of this writing
13
I13 (Input 3)
Programmable input 3
Reserved – not used as of this writing
14
I14 (Input 4)
Programmable input 4
Reserved – not used as of this writing
15
ExtFault
External Fault
If this bit is set, the variable frequency drive will stop with a selected PNU 840.29953 function. The behavior is the same
as if there were a change from 1 –> 0 in the Enable signal, with the exception that the variable frequency drive will switch
to the Error status.
The external fault can be reset just like any other fault (with Fault acknowledge (bit 7) or by switching the supply voltage
off and back on).
0: no external fault
1: external fault
2,3
0..15
Setpoint
Setpoint as a percentage
The setpoint is specified as an integer value between -100 % and 100 %:
100% = 4000hex = 16384dec -100% = -4000hex = -16384dec
Table 194. References table for setpoint/actual speed
SN
N2 data type hex
N2 data type decimal
N2 data type percentage
Frequency in decimal
1
0x4000
16384
100
50
2
0x 3000
12288
74
37
3
0x 2000
8192
50
25
4
0x 1000
4096
24
12
5
0x 0000
0
0
0
6
0x F000
61440
–25
12
7
0x E000
57344
–50
25
8
0x D000
53248
–75
37
9
0x C000
49152
–100
50
Table 193. Profile 2: Output bytes 0 and 4, continued
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...