19
Modbus TCP On-Board communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Figure 16. DH1 keypad navigation to ethernet comm settings
In this menu you will be able to scroll through the below settings to setup the communication protocol.
Table 34. EtherNet/IP / Modbus TCP—P20.3
DG1 code
DH1 code
Parameter
Min.
Max.
Unit
Default
ID
Note
P20.4.1
P12.4.1.1
IP Address Mode
1
1500
0 = Static IP
1 = DHCP with AutoIP
P20.4.2
P12.4.1.2
Active IP Address
1507
P20.4.3
P12.4.1.3
Active Subnet Mask
1509
P20.4.4
P12.4.1.4
Active Default Gateway
1511
P20.4.5
P12.4.1.5
MAC Address
1513
P20.4.6
P12.4.1.6
Static IP Address
192.168.1.254 1501
P20.4.7
P12.4.1.7
Static Subnet Mask
255.255.255.0 1503
P20.4.8
P12.4.1.8
Static Default Gateway
192.168.1.1
1505
—
P12.4.1.9
Enable BACnet IP
0
1
0
1725
0 = Disable
1 = Enable