150
SmartWire-DT External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
SmartWire-DT cable
Table 183. Recommendation for 8 core flat cable
8-pin SWD4-8MF2 ribbon connectors need to be connected
at the beginning and at the end of the ribbon cable.
Ribbon cables are available in various lengths and
configurations. See table below:
Flat band conductor
Description
SWD4-100LF8-24
100-m long roll for making custom
SmartWire-DT cables
SWD4-3LF8-24-2S
SWD4-5LF8-24-2S
SWD4-10LF8-24-2S
Prefabricated cable (with lenght of 3, 5, or 10m)
with two 8-pin SWD4-8MF2 ribbon connectors
All SmartWire-DT modules inside a control panel need to be
connected to the ribbon cable using an 8-pin SWD4-8SF2-5
external device plug.
Figure 59. External device plug SWD4-8SF2-5
Table 184. Recommendation for 5 core round cable
The SmartWire-DT round cable is used as a connecting
cable for connecting to the SmartWire-DT communication
system. The SmartWire-DT round cable is the only way
to guarantee error-free transmissions up to the maximum
possible SmartWire-DT network length of 600 m.
Prefabricated cables with two M12 plug connectors
(socket, plug)
Cable
Description
SWD4-M1LR5-2S
SWD cable, 5-pole, 0.1m, M12-M/M12-F
SWD4-M3LR5-2S
SWD cable, 5-pole, 0.3m, M12-M/M12-F
SWD4-M6LR5-2S
SWD cable, 5-pole, 0.6m, M12-M/M12-F
SWD4-1LR5-2S
SWD cable, 5-pole, 1.0m, M12-M/M12-F
SWD4-1M5LR5-2S
SWD cable, 5-pole, 1.5m, M12-M/M12-F
SWD4-2LR5-2S
SWD cable, 5-pole, 2.0m, M12-M/M12-F
SWD4-3LR5-2S
SWD cable, 5-pole, 3.0m, M12-M/M12-F
SWD4-5LR5-2S
SWD cable, 5-pole, 5.0m, M12-M/M12-F
SWD4-10LR5-2S
SWD cable, 5-pole, 10.0m, M12-M/M12-F
Gateways for using SmartWire-DT module
The DXG-NET-SWD SmartWire-DT interface module‘s
interoperability is guaranteed with the following
SmartWire-DT gateway versions (and higher):
Table 185. Firmware versions of SmartWire-DT
gateways
SmartWire-DT gateway
Firmware Version
EU5C-SWD-CAN
V 1.30
EU5C-SWD-DP
V 1.30
Fieldbus description files
The DXG-NET-SWD SmartWire-DT interface module‘s
interoperability is guaranteed with the following versions
(and higher) of the fieldbus description file for the gateways
listed below
Table 186. Compatible field bus description files
SmartWire-DT gateway
Description file
EU5C-SWD-CAN
from EU5C-SWD-CAN_V130.eds Rev.42
EU5C-SWD-DP (Intel-based CPU)
from Moel14.gsd (V. 1.19)
EU5C-SWD-DP (Motorola-based CPU) from Moel14.gsd (V. 1.18)
SWD master (i. e. XV100)
from ASIC FW Version 2.01 Build: 0081
SWD-Assist
The SWD-Assist program provides valuable support in the
engineering of your SmartWire-DT topology. SWD-Assist is
software that runs under operating systems Windows 2000
(SP 4), Windows XP, Windows Vista (32-bit) or Windows 7
and relieves you of the planning work required for an SWD
topology.
The DX-NET-SWD… SmartWire-DT interface module can be
used in SWD-Assist version V 2.50 and higher.
The SWD-Assist program can be downloaded for free on
the Internet at: http://downloadcenter.moeller.net
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...