64
EtherNet/IP On-Board Communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Input instances
Assembly instance 70
Table 81. Instance 70 (Input) length = 4 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Running1
Faulted
1
2
Speed Actual (Low Byte), rpm
3
Speed Actual (High Byte), rpm
Assembly instance 71
Table 82. Instance 71 (Input) length = 4 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AtReference RefFromNet CtrlFromNet Ready
Running2
Running1
Warning
Faulted
1
Drive State
2
Speed Actual (Low Byte), rpm
3
Speed Actual (High Byte), rpm
Refer “State transition diagram,” provided under “Control Supervisor Object” and
“Drive State” table specified at end of “Input Instances” section.
Drive
State
0x00
DN_NON_EXISTANT
0x01
DN_STARTUP
0x02
DN_NOT_READY
0x03
DN_READY
0x04
DN_ENABLED
0x05
DN_STOPPING
0x06
DN_FAULT_STOP
0x07
DN_FAULTED