147
SmartWire-DT External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
SmartWire-DT External Communication Cards
SmartWire-DT is an intelligent wiring system and makes
for a reliable and easy connection of switching devices,
pilot devices and I/O components with overriding bus
systems possible. The components that are connected with
SmartWire-DT are linked, e.g. to SMARTWIRE-DT -DP or
CANopen communication networks via gateways using
SmartWire-DT masters.
With the SmartWire-DT system, up to 99 modules can
be connected to form a network. Modules can include
SmartWire-DT I/O modules or SmartWire-DT modules
for contactors, soft starters, drives or pilot devices.
The electrical connection is effected via a special 8-pole
connecting cable and the relevant plugs.
When equipped with a DXG-NET-SWD; SmartWire-DT
interface module, the variable frequency drives can be
connected to a SmartWire-DT system and, as a result,
to a higher-level PLC. SmartWire-DT can then be used
to configure, control, and monitor these devices.
SmartWire-DT specifications
Table 180. SmartWire-DT technical data
Items
Value
Electrical and thermal
safety standards
UL 508C, CSA C22.2
IEC/EN 61800-5-1
Ambient Operating
Temperature
-10°C to +50°C IH, with de-rating up to 60 °C
Storage Temperature
-40°F (-40°C) to 158°F (70°C)
Vibration
1G at 15.8—150 Hz
Interface Connector
8-pin Flat Connector/5-pin M12 Connector
Transfer cable
IP20: SmartWire-DT 8-pin ribbon cable
IP54: 5 pin round cable
Max. current
consumption
IP20: 75mA@15VDC
IP54: 75mA@24VDC
Line length depends on different transmission speeds.
Table 181. Line length
A SmartWire-DT network can have a length of up to 600 m.
The actual maximum length will depend on the baud rate
and cable type (ribbon cable or round cable) being used.
Baud rate
Ribbon cable
Round cable (5-pole)
125KB
600m
600m
250KB
600m
600m
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...