17
Modbus TCP On-Board communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Figure 13. Module and network status
Module status indications
Represents the state of the drive.
Table 32. Module status LED description
Indicator state
Summary
Meaning
Steady Off
No power
No power is supplied to the device.
Steady Green
Device operational
Device is operating correctly.
Flashing Green
Standby
Device has not been configured.
Flashing Red
Minor fault
Device has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady Red
Major fault
Device has detected a non-recoverable major fault.
Flashing Green/Red
Self-test
Device is performing its power up testing.
Flash rate is 1 flash per second.
Network status indications
Represents the state of the Ethernet port network interface.
Table 33. Network status LED description
Indicator state
Summary
Meaning
Steady Off
Not powered, no IP address
Device is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing Green
No connections
An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady Green
Connected
At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing Red
Connection timeout
Device is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady Red
Major fault
Device has detected a non-recoverable major fault.
Flashing Green/Red
Self-test
Device is performing its power up testing.
Flash rate is 1 flash per second.
Module Status
Network Status
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...