Page
4-10
www.eaton.com
IB02602002E
MP-4000
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE #
DISPLAY
HELP MESSAGE
SETTING RANGE/VALUE
(DEFaUlT SElECTION aND
ValUE aS ShIPPED IN BOlD)
VALUE SELECTED
5
Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
UB a ON
, UB T ON, and
UB OFF
6
Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
WD a ON
, WD T ON, and
WD OFF
7
Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
MB a ON
, MB T ON, and
MB OFF
8
Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
lB a ON
, LB T ON, and
LB OFF
9
Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
aX a ON
, AX T ON, and
AX OFF
10
Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
SX a ON
, SX T on, and
SX OFF
11
Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between TBS T ON and
TBS OFF
12
RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between
RTDF ON
and RTDF OFF
13
RCOM ON
or
RCOM OFF
ENABLE RTD MODULE
COMMUNICATION FAILURE TO
ACTIVATE ALARM RELAY OR DISABLE
Toggles between
RCOM ON
and RCOM OFF
14
IOCT ON
or
IOCT OFF
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between IOCT ON and
IOCT OFF
15
PH R ON
or
PH R OFF
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
Toggles between PH R ON and
Ph R OFF
16
INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between INSQ ON and
INSQ OFF
17
REMT ON
or
REMT OFF
ENABLE REMOTE TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between REMT ON and
REMT OFF
18
DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between DIFT ON and
DIFT OFF
19
INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between INCT ON and
INCT OFF
20
TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between TRNT ON and
TRNT OFF
21
ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between ZSWT ON and
ZSWT OFF
22
TBYP ON
or
TBYB OFF
ENABLE TRIP BYPASS TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between TBYP ON and
TByP OFF
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...