www.eaton.com
Page
4-11
MP-4000
IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE #
DISPLAY
HELP MESSAGE
SETTING RANGE/VALUE
(DEFaUlT SElECTION aND
ValUE aS ShIPPED IN BOlD)
VALUE SELECTED
PaGE 9, SP aUX 1 SETTINGS FOR aUX 1 RElay OUTPUT CONFIGURaTION
1
LSPU XXX
LOAD SHED PICK-UP CURRENT AS
% OF FLA
50-150%,
OFF
(1% increments)
NOTE: P9L1 and P9L2 are forced to be
coherent. Refer to Section 5 for details.
2
LSDO XXX
LOAD SHED DROP-OUT CURRENT AS
% OF FLA
50-LSPU Value %,
OFF
(1% increments)
NOTE: P9L1 and P9L2 are forced to be
coherent. Refer to Section 5 for details.
3
LSDL XX
LOAD SHED DELAY IN SECONDS
0-5 sec. (0.1 sec. Increments)
If LSPU and LSDO are both set to OFF, the
SP AUX1 functions below are available and
visible.
(1)
4
Choose:
GF A ON
GFT ON
or
GF OFF
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between GF A ON, GF T ON, and
GF OFF
5
Choose:
I2T A ON
I2T T ON
or
I2T OFF
ENABLE I2T ALARM OR TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between I2T A ON,
I2T T ON
, and
I2T OFF
6
Choose:
JAM A ON
JAM T ON
or
JAM OFF
ENABLE JAM ALARM OR TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between JAM A ON, JAM T ON, and
jaM OFF
7
Choose:
UL A ON
UL T ON
or
UL OFF
ENABLE UNDERLOAD ALARM OR TRIP
TO ACTIVATE AUX1 RELAY OUTPUT
OR DISABLE
Toggles between UL A ON, UL T ON, and
Ul
OFF
8
Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between UB A ON, UB T ON, and
UB OFF
9
Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between WD A ON, WD T ON, and
WD OFF
10
Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between MB A ON, MB T ON, and
MB OFF
11
Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between LB A ON, LB T ON, and
lB OFF
12
Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between AX A ON, AX T ON, and
aX OFF
13
Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between SX A ON, SX T ON, and
SX OFF
14
Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
Toggles between TBS T ON and
TBS OFF
15
RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between RTDF ON and
RTDF OFF
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...