Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE #
DISPLAY
HELP MESSAGE
SETTING RANGE/VALUE
(DEFaUlT SElECTION aND
ValUE aS ShIPPED IN BOlD)
VALUE SELECTED
2
GFSD XX
GROUND FAULT START DELAY IN
CYCLES
2-60 ac cycles (1 cycle increments)
(5)
3
GFRD XX
GROUND FAULT RUN DELAY IN CYCLES
0-60 ac cycles (1 cycle increments)
(2)
4
IOC XXX
INSTANTANEOUS OVERCURRENT IN
% FLA
300-1,600%,
OFF
(1% increments)
5
IOCSD XX
INSTANTANEOUS OVERCURRENT
START DELAY IN CYCLES
2-60 ac cycles (1 cycle increments)
(3)
6
JMT XXX
JAM TRIP LEVEL IN % FLA
100-1,200%, OFF (1% increments)
(1,000%)
7
JMSD XX
JAM TRIP AND ALARM START DELAY IN
SECONDS
0-1,200 sec. (1 sec. increments)
(60)
8
JMTR XX
JAM TRIP RUN DELAY IN SECONDS
0-240 sec. (1 sec. increments)
(60)
9
ULT XXX
UNDERLOAD TRIP LEVEL IN % FLA
6-90%,
OFF
(1% increments)
10
ULSD XXX
UNDERLOAD TRIP AND ALARM START
DELAY IN SECONDS
0-120 sec. (1 sec. increments)
(10)
11
ULTR XXX
UNDERLOAD TRIP RUN DELAY IN
SECONDS
0-240 sec. (1 sec. increments)
(10)
12
UBT XXX
PHASE UNBALANCE TRIP LEVEL
4-40%,
OFF
(1% increments)
13
UBSD XXX
PHASE UNBALANCE TRIP AND ALARM
START DELAY IN SECONDS
0-120 sec. (1 sec. increments)
(10)
14
UBTR XXX
PHASE UNBALANCE TRIP RUN DELAY IN
SECONDS
0-240 sec. (1 sec. increments)
(2)
PaGE 4, SP alaRM SETTINGS FOR alaRM EVENTS
1
GFA XXX
GROUND FAULT ALARM LEVEL IN % OF
GROUND CT RATIO NUMERATOR
2-55% OF Ground CT ration numerator,
OFF
(1% increments)
2
I2TA XXX
I2T ALARM LEVEL IN % FULL OF I2T TRIP
CAPACITY
60-99%, OFF (1% increments
)
(80)
3
JMA XXX
JAM ALARM LEVEL IN % FLA
100-1,200%, OFF (1% increments)
(1,000%)
4
JMAR XXX
JAM ALARM RUN DELAY IN SECONDS
0-240 sec. (1 sec. increments)
(2)
5
ULA XXX
UNDERLOAD ALARM LEVEL IN % FLA
6-90%,
OFF
(1% increments)
6
ULAR XXX
UNDERLOAD ALARM RUN DELAY IN
SECONDS
0-240 sec. (1 sec. increments)
(10)
7
UBA XXX
PHASE UNBALANCE ALARM LEVEL
4-40%, OFF (1% increments)
(10)
8
UBAR XXX
PHASE UNBALANCE ALARM RUN DELAY
IN SECONDS
0-240 sec. (1 sec. increments)
(10)
PaGE 5, SP STaRT SETTINGS FOR STaRT EVENTS
1
ST/T XXX
STARTS PER TIME ALLOWED
1-10 starts/time (increments of 1)
(1)
2
T/ST XXX
TIME ALLOWED FOR STARTS COUNT IN
MINUTES
1-240 minutes,
OFF
(1 minute increments)
3
TBS XXX
TIME BETWEEN STARTS IN MINUTES
1-240 minutes,
OFF
(1 minute increments)
4
NOCS X
NUMBER OF COLD STARTS ALLOWED
1-5 starts (increments of 1)
(1)
5
TRNC XXX
MOTOR START TRANSITION CURRENT
LEVEL IN %FLA
10-300% (1% increments)
(130)
6
TRNT XXX
MOTOR START TRANSITION TIME IN
SECONDS
0-1,200 sec. (1 sec. increments
) (10)
7
Choose:
TRN TIME
TRN I
TRN T+C
TRN T/C
TRANSITION ON EVENT
TRN TIME - ON TIME ONLY
TRN I - ON CURRENT ONLY
TRN T+C - ON TIME OR CURRENT
TRN T/C - ON TIME AND CURRENT
Choose one of the four conditions that determine
a start-to-run transition: TRN TIME, TRN I,
TRN T+C
, or TRN T/C
Refer to settings P5L5 and P5L6.
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...