MP-4000
IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE #
DISPLAY
HELP MESSAGE
SETTING RANGE/VALUE
(DEFaUlT SElECTION aND
ValUE aS ShIPPED IN BOlD)
VALUE SELECTED
6
Choose:
UP A ON
UP T ON
UP OFF
ENABLE UNDERPOWER ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between UP T ON, UP A ON,
UP OFF
7
Choose:
PF A ON
PF T ON
PF OFF
ENABLE POWER FACTOR ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between PF T ON, PF A ON,
PF OFF
PaGE 24, SP2 aUX2 SETTINGS FOR aUX 2 RElay OUTPUT CONFIGURaTION
1
Choose:
VU A ON
VU T ON
VU OFF
ENABLE VOLTAGE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between VUT ON, VUA ON,
VU OFF
2
Choose:
OV A ON
OV T ON
OV OFF
ENABLE OVERVOLTAGE ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between OVT ON, OVA ON,
OV OFF
3
Choose:
UV A ON
UV T ON
UV OFF
ENABLE UNDERVOLTAGE ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UVT ON, UVA ON,
UV OFF
4
Choose:
OF A ON
OF T ON
OF OFF
ENABLE OVERFREQUENCY ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between OF T ON, OF A ON,
OF OFF
5
Choose:
UF A ON
UF T ON
UF OFF
ENABLE UNDERFREQUENCY ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UF T ON, UF A ON,
UF OFF
6
Choose:
UP A ON
UP T ON
UP OFF
ENABLE UNDERPOWER ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UP T ON, UP A ON,
UP OFF
7
Choose:
PF A ON
PF T ON
PF T OFF
ENABLE POWER FACTOR ALARM OR
TRIP TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
Toggles between PF T ON, PF A ON,
PF OFF
PaGE 25, SP2 SyS SETTINGS FOR SySTEM CONFIGURaTION
1
WH XXX
SETTING FOR ACTIVE ENERGY WATT-
HOUR DISPLAY - NORMAL OR KILO OR
GIGA
Select
KIlO
, MEGA, or GIGA
2
VARH XX
SETTING FOR REACTIVE ENERGY
VARH DISPLAY - NORMAL OR KILO OR
GIGA
Select
KIlO
, MEGA, or GIGA
3
VAH XXX
SETTING FOR APPARENT ENERGY VAH
DISPLAY - NORMAL OR KILO OR GIGA
Select
KIlO
, MEGA, or GIGA
4
WATT XXX
SETTING FOR ACTIVE POWER WATT
DISPLAY - NORMAL OR KILO OR MEGA
Select NORMAL,
KIlO
, or MEGA
5
VAR XXX
SETTING FOR REACTIVE POWER VAR
DISPLAY - NORMAL OR KILO OR MEGA
Select NORMAL,
KIlO
, or MEGA
6
VA XXX
SETTING FOR APPARENT POWER VA
DISPLAY - NORMAL OR KILO OR MEGA
Select NORMAL,
KIlO
, or MEGA
7
PTR XXX
RATIO OF EXTERNAL PT
1 - 250:1, 0.01 increments (
34.6
)
8
XFMR XXX
XFMR CONFIGURATION - SELECT -
WYE, DELTA, OPEN DELTA
Select 0 = WYE, 1= DELTA, 2 =
OPEN
DElTa
9
VOLT XXX
SETTING FOR VOLTAGE DISPLAY -
VOLTS OR KILO VOLTS
Select VOLTS or
KIlOVOlTS
PaGE 26, SP COMM SETTINGS FOR RS-232 COMMUNICaTIONS
1
232 XXX
RS232 COMMUNICATION - ON OR OFF
Select RS-232 communications, either ON or
OFF
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...