Page
1-2
www.eaton.com
IB02602002E
MP-4000
12. RTD diagnostics and communications error checking for addi
-
tional security against operation from RTD failures.
13. Mechanical Process Load Shedding feature provides overload
indication to control upstream processes, averting unnecessary
motor overload shutdown or jam trips, and maintaining process
continuity.
14. Download settings or retrieve metered and historical values via
the communications port.
15. Flexible User-configurable inputs and outputs for broader applica
-
tion.
16. Options for transition function control and monitoring on time
and/or current.
17. Emergency override function resets jogging limit functions and
clears thermal-model bucket to permit restart with a time-tagged
event log. Unit uses a secured button; this function can be dis
-
abled.
18. MP-4000 can be programmed while the motor runs, and new set
-
tings are all put into effect at once in a controlled fashion. Or, the
User can set the unit so programming is allowed only after motor
stop.
1.3 Use of This Manual
This manual contains the following sections:
Section 1 - Introduction - Describes the upgrade changes
from the existing MP-3000 to the MP-4000 including retrofit
and new features list.
Section 2 - Product Overview - Includes benefits, feature
list, use of manual, and list of options.
Section 3 - Specifications - Provides hardware specifics
Section 4 - Operator Panel - Describes the pushbuttons,
LEDs, display window, and security door on the MP-4000’s
faceplate plus the different modes of operation and detailed
mode description tables.
Section 5 - Programming the MP-4000 - Gives specific guid
-
ance for selecting and setting values.
Section 6 - Installation and Wiring - Outlines procedures for
the plant electrician to follow when installing and wiring the
MP-4000.
Section 7 - Start-Up - Lists step-by-step procedures for
energizing the MP-4000 for the first time after installation.
•
•
•
•
•
•
•
Section 8 - Motor Thermal Protection Basics–Gives an over-
view of how the hardware and software function together to
control, monitor, and protect the motor.
Section 9 - Application and Settings - Is intended as an aid
to the application engineer considering how and when to
apply the various features of the MP-4000.
Section 10 - Data Communications - Describes what is
needed for the MP-4000 to communicate with host com
-
puter systems.
Section 11 - Testing - Describes how to use the MP-4000
test functions and details recommended maintenance.
Section 12 - Troubleshooting - Provides information on how
to use the Operator Panel to recognize malfunctions. Also,
gives specific troubleshooting procedures.
Section 13 - Drawout Case Option - Describes installing and
using MP-4000 drawout case models.
Once the User is familiar with the basics of operating the MP-4000,
Tables 4.1 through 4.5 can be used as guides to program and monitor
the MP-4000.
The following accessories and options are covered in other instruction
manuals:
Table 1.1 MP-3000 accessories and Options.
URTD module for
connecting RTDs
to the MP-4000
(1)
I.L. 17367
IQ DC Power Supply,
100-150 Vdc
I.L. 17286
INCOM PONI (IPONI)
I.L. 17547
Ethernet PONI (EPONI)
I.L. 17560
Other PONI Types
Consult Eaton distributor or
Eaton.com website
DPONI Types
I.L. 17559
(1)
This MP-4000 Instruction Manual (IM) gives all basic information
on installing the URTD module.
NOTE:
Some manuals will be supplied electronically on the CD
shipped with the MP-4000.
•
•
•
•
•
•
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...