Refer to Table 12.3 for OPTO ERR.
2.
Setting P12L16 permits a choice as to whether these internal
failures produce alarm plus trip, or just an alarm.
Table 12.3 Troubleshooting Operator Panel Malfunctioning.
Symptom
Probable Cause
Solution
All LEDs and displays are off or
unintelligible.
Incoming ac deficient.
MP-4000 malfunctioning.
The MP-4000 operates down to 55% of
rated voltage, but such a low voltage is
not normal and should be diagnosed.
Verify that 120 or 240 Vac (±15%) exists
between terminals 4 and 7.
Remove ac power completely for 10
seconds and reapply it. If the problem
persists, return the MP-4000 to the fac
-
tory for repair.
OPTO ERR message
An optocoupler failure trip based on bad
timing of ac input waveform zero
crossings
Check the frequency setting P1L7 for
50 or 60 Hz, as appropriate. Make sure
120 Vac is used for discrete inputs.
Energizing with dc causes this error
message.
Table 12.4 Internal Diagnostic Failure Messages.
Display
Complete help Message
A/D ERR
A/D CONVERTER ERROR TRIP
RAM ERR
RAM ERROR TRIP
ROM ERR
ROM ERROR TRIP
OPTO ERR
OPTOCOUPLER FAILURE TRIP
1
ZRAM ERR
NON VOLATILE MEMORY ELEMENT SHOULD BE
REPLACED
FLASHERR
FLASH WRITING ERROR
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...