Page
3-2
www.eaton.com
IB02602002E
MP-4000
alarm Setting Range
Ground Fault:
Off, 2% to 55% CT Ratio
Overload I
2
t:
Off, 60 to 99% I
2
t
Jam:
Off, 100 to 1,200% FLA
Underload:
Off, 6 to 90% FLA
Phase Unbalance:
Off, 4 to 40% I
2
/I
1
Run Delay Timers:
Off, 0 to 240 sec.
Phase Unbalance Alarm Threshold
Off, 1 to 100 V
Phase Unbalance Alarm Run Delay Off, 1 to 1,200 sec.
Underfrequency Alarm Threshold
Off, 15 to 60 Hz
Under frequency Alarm run Delay
Off, 0 to 60 sec.
Voltage Unbalance Alarm
Off, 0 to 480 sec.
Overfrequency Alarm Threshold
Off, 15 to 70 Hz
Overfrequency Alarm Run Delay
0 to 60 sec.
Overvoltage Main Alarm Threshold
Off, 10 to 150 V
Overvoltage Main Alarm Run Delay
Off, 0 to 480 sec.
Main UV Alarm Run Delay
Off, 0 to 60 sec.
Under Power Alarm Threshold
Off, 0.06 to .90 *FLA *VT
Underpower Alarm Run Delay
Off, 0 to 480 sec.
Leading Power Factor Alarm Threshold 1 Off, 0.05 to 0.99
Lagging Power Factor Alarm Threshold 2 Off, 0.05 to 0.99
Power Factor Alarm Start Delay
Off, 0 to 60 sec.
Power Factor Alarm Run Delay
Off, 0 to 60 sec.
Start Control Functions
Starts per Time:
1 to 10 starts
Time for Starts per Time:
Off, 1 to 240 min.
Time Between Starts:
Off, 1 to 240 min.
Number of Cold Starts:
1 to 5 starts
Motor Transition Current:
10 to 300% FLA
Time for Transition:
0 to 1,200 sec.
Incomplete Sequence Timer:
Off, 1 to 240 sec.
Long Acceleration Timer:
Off, 1 to 1,200 sec.
Antibackspin Timer:
Off, 1 to 3,600 sec.
RTD Inputs (Requires URTD module)
Sensor Types:
10 ohm copper
100 ohm nickel
120 ohm nickel
100 ohm platinum
URTD Module Communications
Interface:
Plastic optical fiber
(preferred)
Electrical (3-wire)
Fiber Optic Cable:
Type HFBR-ELS (length) -
precut low-loss with
connectors
Type HBFR-EUS (length) -
bulk low-loss without
connectors
Type HBFR-RLS (length) -
standard-loss, acceptable
for <10m (<32.8 ft)
Clock
Accuracy:
Freerunning ± 1 min./mo.
@ 25°C (77°F). Automati
-
cally updated by PowerNet
host.
IPONI Communications
(Section 10 contains more protocols.)
Type:
2-wire, 115.2 kHz carrier
Baud Rate:
1,200 ASK or 9,600 FSK
Max. Distance:
10,000 ft (3048 m)
Protocol:
INCOM
Functions:
Read/write setpoints
Read metered values
Read trip/alarms
Read events
Read history
Reset history
Reset functions
Emergency override
Trip
View starting profile
logging
Log Book:
100 events
Log Event:
20 trips and alarms
Log Start:
Last 4 starts
Start Profile:
Last 4 starts (communications
port only)
History Records:
Motor, trips, alarms, and totals
Environmental Ratings
Operating Temp.:
-20 to + 60°C (-4 to +140°F)
Storage Temp.:
-45 to + 85°C (-49 to +185°F)
Humidity:
0 to 95% non-condensing
Dimensions (Fixed Mount Case Only)
Height:
10.25 in. (260.4 mm)
Width:
6.72 in. (170.7 mm)
Depth:
4.3 in. (109.2 mm)
Weight:
5 lbs. (2.3 kg)
8.0 lbs. (3.6 kg) (with URTD
and PONI)
Standards
ANSI/IEEE C37.90-1989
Standard for Relay Systems Associated with Electric Power Apparatus.
ANSI/IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems
ANSI/IEEE C37.90.2-1995
Standard Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
UL-1053
Ground Fault Sensing and Relaying Equipment
Emissions (EN-50081-2)
EN 50011 CISPR-11, Class A, CFR 47 FCC Part 15
Subpart b Class A
EN-61000-6-2
Immunity
EN 61000-4-2
ESD
EN 61000-4-3
RF Radiated Immunity
EN 61000-4-4
EFT/Burst Immunity
EN 61000-4-5
Surge Immunity
EN 61000-4-6
RF Conducted Immunity
EN 61000-4-8
Power Frequency Magnetic Field Immunity
EN 61000-4-11
Voltage Variation Immunity
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...