www.eaton.com
Page
4-25
MP-4000
IB02602002E
Table 4-5. log Mode Display.
SUB-
MENU
LINE
DISPLAY
COMPLETE HELP MESSAGE
DESCRIPTION
EMRG OVR
EMERGENCY OVERRIDE EVENT -
AN EMERGENCY OVERRIDE WAS
PERFORMED
Emergency override can be activated from the front face plate, from a programmed discrete
input, or over the communications network.
DATE OF LOGGED EVENT
Date that event occurred.
TIME OF LOGGED EVENT
Time that event occurred.
SET CHNG
PROGRAM MODE EXIT - POSSIBLE
SET POINT CHANGES
Recorded every time the program mode is normally exited. This can occur with the second
press of the Prog pushbutton, or over the communications network.
MM/DD/YY
DATE OF LOGGED EVENT
Date that event occurred.
HH.MM.SS
TIME OF LOGGED EVENT
Time that event occurred.
RESET
RESET EVENT - A RESET EVENT
CLEARED A TRIP OR ALARM
Logged only when a trip or alarm event was cleared. This can be done through the front
face panel Reset pushbutton, by a programmed discrete input activation, or over the
communications network.
MM/DD/YY
DATE OF LOGGED EVENT
Date that event occurred.
TRIP
BYPASS
TRIP BYPASS < JUMPER BYPASS OF
MP-4000 TRIP RELAY >
MM/DD/YY
DATE OF LOGGED EVENT
Date that event occurred.
HH.MM.SS
TIME OF LOGGED EVENT
Time that event occurred.
PH UNBAL
PHASE UNBALANCE TRIP
HH.MM
TIME OF LOGGED EVENT
Time that event occurred.
TRIP
(Description of trip event)
For a complete list of trips with help messages, refer to the trip conditions in Table 12.2 and
the internal diagnostics failure messages in Table 12.4.
MM/DD/YY
DATE OF LOGGED EVENT
Date that event occurred.
HH.MM
TIME OF LOGGED EVENT
Time that event occurred.
ALARM
(Description of alarm event)
For a complete list of alarms with help messages, refer to the alarm conditions in Table 12.2
and the internal diagnostics failure messages in Table 12.4.
MM/DD/YY
DATE OF LOGGED EVENT
Date that event occurred.
HH.MM
TIME OF LOGGED EVENT
Time that event occurred.
LOG
EVNT
DETAILED LOG OF THE LAST 20
ABNORMAL EVENTS
This page contains detailed troubleshooting information for all trip and alarm events. The
events are logged chronologically. From this display, press the line up pushbutton to get
the most recent event. Press it again for the next most recent event and so on. From this
display, press the line down pushbutton to get the oldest event. Press it again for the next
oldest event.
T BYPASS
TRIP BYPASS < JUMPER BYPASS OF
MP-4000 TRIP RELAY >
A trip or alarm event was logged. For a complete list, refer to the trip conditions in Table
12.2 and the internal diagnostics failure messages in Table 12.4.
MM/DD/YY
DATE OF EVENT
Date that event occurred.
HH.MM.SS
TIME OF EVENT
Time that event occurred.
IA XXX
PHASE A CURRENT IN AMPS AT TIME OF
EVENT
Phase current in amps at time of trip.
IB XXX
PHASE B CURRENT IN AMPS AT TIME OF
EVENT
IC XXX
PHASE C CURRENT IN AMPS AT TIME OF
EVENT
IG XXX
GROUND FAULT CURRENT IN AMPS AT
TIME OF EVENT
Ground fault current in amps at time of trip.
%I2T XXX
PERCENT OF I2T TRIP LEVEL AT TIME OF
EVENT
Percentage of thermal bucket used at time of trip.
%UB XXX
PHASE UNBALANCE AT TIME OF THE
EVENT - IF POSITIVE THE RATIO OF
NEGATIVE TO POSITIVE SEQUENCE
CURRENT - IF NEGATIVE THE INVERSE
Percentage of sequence current unbalance at time of trip.
WT1 XXX
WINDING TEMP 1 IN DEGREES (F OR C)
AT TIME OF EVENT
RTD temperatures at time of trip.
WT2 XXX
WINDING TEMP 2 IN DEGREES (F OR C)
AT TIME OF EVENT
RTD temperatures at time of trip.
WT3 XXX
WINDING TEMP 3 IN DEGREES (F OR C)
AT TIME OF EVENT
RTD temperatures at time of trip.
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...