The negative sequence current I
2
is a three-phase current component
with a reverse phase rotation compared to that of the ac source. This
current generates a reverse torque in the second rotor, and works
against the main action of the motor, doing negative work. Because
the negative work caused by I
2
stays within the rotor, it is completely
absorbed as heat and, therefore, has a far more significant effect on
the rotor heating than the balanced l
1
.
Phasor analysis is used to determine the sequence currents from
physical phase current phasors.
Any three-phase ac current without
external ground or neutral return path can be represented by the
addition of I
1
and I
2
phasors in each phase. For an example, refer to
the unbalanced motor currents of Figure 8.3. In this case, the three-
phase currents in the motor are I
A
, I
B
, and I
C
. Note that I
B
and I
C
are of
about the same
magnitude
as I
A
, yet are noticeably displaced in
phase
position
. This is an example of a serious negative sequence condi
-
tion that is threatening to the rotor, yet is not reflected in the current
magnitudes alone.
To calculate the positive sequence component in phase A, rotate the
phase B current phasor 120 degrees in the positive direction and the
phase C phasor 240 degrees in the positive direction. See Figure 8.4.
The formula for I
A1
is:
I
A1
= I
A
+ (I
B
120°) +( I
c
240°)
3
Note that these are phasor (vector) operations with a phasor result.
The positive sequence phasors in phases B and C have the same
magnitude as the phase A positive sequence phasor, but lag the
phase A component by exactly 120 and 240 degrees, respectively.
This balanced set of phasors drives the motor’s useful work.
To calculate the negative sequence component in phase A, rotate the
phase B current phasor 120 degrees in the negative direction and the
phase C phasor 240 degrees in the negative direction. See Figure
8.5. The formula for I
A2
is:
I
A2
= I
A
+ (I
B
-120°) + (I
c
- 240°)
3
The negative sequence phasors in phases B and C have the same
magnitude as the phase A positive sequence phasor, but lead the
phase A component by exactly 120 and 240 degrees, respectively.
This balanced set of phasors represents the net effect of magnitude or
phase unbalance and only heats the rotor.
Certain harmonics in the phase currents produce torques in the rotor,
just like positive and negative sequence currents. In particular, the 7
th
and 13
th
and certain higher harmonics act like positive sequence. The
5
th
, 11
th
, and certain other higher harmonics act like negative sequence.
This can also influence motor performance and heating. The
MP-4000 sequence calculations also capture these harmonic currents
and include their effect in the thermal modeling.
Prior to the use of a microprocessor in a multifunction motor protec
-
tion relay, there was no reasonable way of modeling the total heating
effects of the positive and negative sequence components on a con
-
tinuous basis. Therefore, oversimplified assumptions were used with
available relays. This resulted both in nuisance tripping and in motor
burnouts or life reduction. The MP-4000 uses a unique, patented
calculation for determining these values from current samples and
modeling their effects. The effective current squared, as used in the
calculation for rotor heating, is:
I
2
=
I
1
2
+
kI
2
2
Here,
I
2
is weighted by k because of the disproportionate heating
caused by the negative sequence current component. The effects
of both the positive and negative sequence currents are accurately
taken into account. Their combined
effect is incorporated into a rotor
protection algorithm that effectively keeps track of the temperature of
the rotor.
It is not necessary to pick an arbitrary phase unbalance setting to trip
the motor, although such an unbalance trip function is additionally
included in the relay to speed up tripping without heating for grossly
unbalanced conditions. As long as the combined effect of the positive
and negative sequence currents does not approach the values in the
motor protection curve, the MP-4000 allows the motor to run.
8.2.3 Thermal Bucket
The MP-4000 models heating as the filling of a thermal reservoir or
accumulating bucket whose size is determined by the thermal capac
-
ity of the motor. This capacity is calculated in the relay from motor
nameplate constants. The filling is proportional to effective I
2
over
time, where effective I
2
includes the disproportionate heating effect of
negative sequence currents. Cooling is also modeled as draining of
the bucket. The loss of equilibrium between heating and cooling leads
to an eventual thermal trip. The thermal bucket filling in percent can be
observed continuously on the MP-4000 display, via data communica
-
tions, or via the 4-20 mA transducer output.
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...