When the trip relay is operating in Mode 2, the normally closed con-
tact, which would be open during normal operation in Mode 2, shorts
when the inner chassis is removed.
The “relay out of service” alarm available in the MP-3000 is no longer
available in the MP-4000.
13.4.3 armed/Disarmed Operation
The ARMED/DISARMED feature is most useful when the relay is
fitted in the optional drawout case. This feature blocks operation of
the trip output contacts, but not the protection displays. This permits
the insertion of the relay without risk of tripping a critical motor due
to improper setting. The relay provides a relay alarm and trip status
indication. If this occurs upon insertion, the User has the option to
review applicable protection settings to verify they are correct. Refer
to Subsections 5.12.18 and 9.2.7 for more information on the proper
application and considerations of the ARM/DISARM feature.
NOTE:
The relay must be placed into the ARMED mode before
completing the installation. Failure to do so disables the motor
protection, and may result in serious motor and equipment
damage.
13.5 Drawout Operation
13.5.1 Inserting the Relay
Before the MP-4000 is inserted into the Drawout Outer Case:
• Verify that all wiring is correct as shown in the wiring
diagram.
• Set the INCOM communication device address.
• If the URTD fiber optic cable is used, refer to Subsection
13.3.1 for special instructions concerning the proper installa
-
tion of the fiber.
When inserting the MP-4000 Inner Chassis in the drawout outer case,
use the guides to align the exterior of the inner chassis with the interior
of the outer case. Slide the unit into the case using the guides, press
-
ing firmly until all four latches on the sides of the device are seated
and latched into place. Tabs on the MP-4000 Drawout Inner Chassis
prevent the inner chassis from being inserted upside down or being
inserted into an outer case of another relay or IQ metering product.
CaUTION
ThE MP-4000 INNER ChaSSIS MUST BE FUlly INSERT-
ED aND FUlly laTChED INTO ITS DRaWOUT OUTER
CaSE FOR PROPER OPERaTION OF ThE DEVICE.
When the unit is seated properly, the quick release buttons at the top
and bottom of the unit return to their non-compressed position. The
device can now be secured in the outer case by inserting a locking
ring or meter seal in the provided slot.
13.5.2 Removing the Relay
WaRNING
REMOVal OF ThE MP-4000 INNER ChaSSIS FROM ThE
DRaWOUT OUTER CaSE EXPOSES lIVE PaRTS, WhERE
ThE haZaRD OF a FaTal ElECTRIC ShOCK IS PRES-
ENT. alWayS DISCONNECT aNy CONTROl OR SOURCE
POWER BEFORE TOUChING aNyThING ON ThE INTER-
Nal OR EXTERNal PaRTS OF ThE DRaWOUT OUTER
CaSE.
When removing the Inner Chassis from the Drawout Outer Case, first
remove any locking ring that has been installed. Press the top and
bottom quick release buttons simultaneously, and pull the relay out by
its front panel.
NOTE:
If the URTD fiber cable is used, refer to Subsection 13.3.2 for
proper removal of the relay to prevent damage to the fiber optics.
13.6 Warranty and liability Information
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OF
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS
CONTAINED HEREIN.
In no event will Eaton Inc. be responsible to the purchaser or User in
contract, in tort (including negligence), strict liability, otherwise for any
special, indirect, incidental, or consequential damage or loss what
-
soever, including but not limited to damage or loss of use of equip
-
ment, plant or power system, cost of capital, loss of power, additional
expenses in the use of existing power facilities, or claims against the
purchaser or User by its customers resulting from the use of the infor
-
mation and descriptions contained herein.
13.7 Technical assistance
For additional information, technical assistance, or referral to a local
authorized distributor, contact Power Management Applications Sup
-
port at 1-800-809-2772, Option 4, or
www.eaton.com
and follow the
power management products link.
Summary of Contents for MP-4000
Page 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Page 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Page 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Page 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Page 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Page 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Page 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Page 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Page 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Page 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Page 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...