The value of the operating hours in OT are retained when you reset the hours counter with a
signal at input R. The hours counter OT continues the count as long as En = 1, irrespective of
the status at the reset input R. The counter limit of OT is 99999 h. The hours counter stops
when it reaches this value.
In programming mode, you can set the initial value of OT. The counter starts operation at any
value other than zero. MN is automatically calculated at the START, based on the MI and OT
values.
Example: MI = 100, OT = 130, the result is MN = 70
Parameter
Parameter
Parameter
Parameter preset
preset
preset
preset
In xLogicsoft, you can define MI and an OT start value.
You determine that Q does not depend on En by selecting the corresponding check box.
Retentivity
Retentivity
Retentivity
Retentivity with
with
with
with the
the
the
the hours
hours
hours
hours counter
counter
counter
counter
The hours counter in the xLogic is generally retentive.
However, if the values of the hours counter are lost after a power failure, then select the
respective block in your circuit program. Right mouse click on the hours counter and select
Block
Block
Block
Block Properties
Properties
Properties
Properties >
>
>
> Parameters
Parameters
Parameters
Parameters
. The option
Retentivity
Retentivity
Retentivity
Retentivity
must be activated and not
changeable (grayed out).
If the
Retentivity
Retentivity
Retentivity
Retentivity
option is not available, then delete the block and insert a new special
function
hours
hours
hours
hours counter
counter
counter
counter
at the same position.
4
4
4
4.4.15
.4.15
.4.15
.4.15 Threshold
Threshold
Threshold
Threshold trigger
trigger
trigger
trigger
Short
Short
Short
Short description
description
description
description
The output is switched on and off, depending on two configurable frequencies.
Parameter
Parameter
Parameter
Parameter
Connection
Connection
Connection
Connection
Description
Description
Description
Description
Input Fre
The function count 0 to 1 transitions at input Fre. ! to 0
transitions are not counted.
Use
•
Inputs I5,I6,I7,I8(ELC-12) or IB/IC(ELC-18) for
fast counts
max. 14 kHz (I5,I6 ),60kHz
(
I7,I8
)
( ELC-12) or 14
kHz (ELC-18).
•
Any other input or circuit element for low
frequencies (typical 4 Hz).
Parameter
On:
On:
On:
On:
On threshold
Range of values: 0000...9999
Off:
Off:
Off:
Off:
Off threshold
Range of values: 0000...9999
G_T:
G_T:
G_T:
G_T:
Time interval or gate time during which the input
pulses are measured.
Range of values: 00:05 s...99:99 s
Output
Q
Q
Q
Q
Q is set or reset according to the threshold values.
Summary of Contents for xLogic
Page 1: ......
Page 2: ......
Page 102: ...100 100 100 100 B B B B Blocks Blocks Blocks Blocks...
Page 105: ...103 103 103 103 G G G G M M M M status status status status...
Page 106: ...104 104 104 104 H H H H AM AM AM AM value value value value...
Page 164: ...162 162 162 162 If the Memory Read block had been triggered the Q1 of ELC 12 CPU will be set 1...
Page 204: ...202 202 202 202 Step Step Step Step 6 6 6 6 Moving Moving Moving Moving...
Page 226: ...224 224 224 224...