4.13
.13
.13
.13 Modbus
Modbus
Modbus
Modbus Write
Write
Write
Write
Short
Short
Short
Short description:
description:
description:
description:
When a high level in En, the Modbus Write block will be activated and the xLogic SuperRelay
could communicate with peripheral as a master via RS232 or RS485 interface, further the
output will be switched on when the communication is established successfully. Otherwise the
output (Q pin) is keep “off” it means communication is failed.
A signal at input R resets output Q and disable, this block at the same time
Connection
Connection
Connection
Connection
Description
Description
Description
Description
Input
En
En
En
En
A high signal at En input will enable “Modbus Write” function block to be activated
Input
R
R
R
R
Reset the value read from peripheral and set the output to 0 via the R (Reset) input.
Reset has priority over En
Parameter
Slave
Slave
Slave
Slave address
address
address
address
: 1 is default .
Communication
Communication
Communication
Communication protocol:
protocol:
protocol:
protocol:
Modbus(RTU)
Communication
Communication
Communication
Communication parameter:
parameter:
parameter:
parameter:
baud rate (BPS),Data bits, Stop bits,
Parity
,
Overtime (response time out)
Comm
Comm
Comm
Comm Type:
Type:
Type:
Type:
RS232 or RS485( Communication interface of xLogic )
Data
Data
Data
Data register
register
register
register Index:
Index:
Index:
Index:
High Low /Low High
Command:
Command:
Command:
Command:
05 Write Single Coil
06 Write Single Register
15 Write Multiple Coils
16 Write Multiple Registers
Register
Register
Register
Register start
start
start
start address,
address,
address,
address, count
count
count
count
Output
Q
Q
Q
Q
Q is set or reset depending on the communication status.
Successful communication , Q=1;
Failed communication ,Q=0;
The
The
The
The Property
Property
Property
Property in
in
in
in dialog
dialog
dialog
dialog box
box
box
box of
of
of
of “
“
“
“Modbus
Modbus
Modbus
Modbus Write
Write
Write
Write”
”
”
” shows
shows
shows
shows as
as
as
as below
below
below
below figure:
figure:
figure:
figure:
Summary of Contents for xLogic
Page 1: ......
Page 2: ......
Page 102: ...100 100 100 100 B B B B Blocks Blocks Blocks Blocks...
Page 105: ...103 103 103 103 G G G G M M M M status status status status...
Page 106: ...104 104 104 104 H H H H AM AM AM AM value value value value...
Page 164: ...162 162 162 162 If the Memory Read block had been triggered the Q1 of ELC 12 CPU will be set 1...
Page 204: ...202 202 202 202 Step Step Step Step 6 6 6 6 Moving Moving Moving Moving...
Page 226: ...224 224 224 224...