Dynamic Flow Computers
SFC332L Manual
Quick Start
— 1-38
Date: 8/1/2019
Calibration of Analog Output:
To calibrate the analog output against the end device follow the following steps:
1. Go to the calibration menu and press <F8>. Scroll down to analog output and press <
ENTER
>
and then <ALT><R>. This will cause the flow computer to output the minimum possible
signal 3.25 mA. Enter the live output value reading in the end device i.e. 3.25 mA and press
<F3> function key. Now the flow computer will output full scale 21.75 mA. Enter the live
output i.e. 21.75 then press the <F3> function key.
2.
Now verify the output against the calibration device.
Multi-Variable Transmitters (Model 205)- DP and Pressure
O
F F S E T C A L I B R A T I O N
1. Induce live value for temperature, pressure, or DP.
2. Go to
Calibration - Multi-Variable
menu.
3. Press <F8>, point to the value being calibrated, enter the correct value followed by
<
ENTER> key
, and then press <F3> function key to download data.
4.
Now read induce live values to verify the calibration.
F
U L L S C A L E C A L I B R A T I O N
1. Press <F8>. Scroll to the parameter to be calibrated, and then press <ALT><R>.
2. Induce the low range signal, then press <
ENTER>
followed by <F3> function key.
3. Induce the low range signal, then press <
ENTER>
followed by <F3> function key.
4.
Now verify the live reading against the flow computer reading
.
T
O U S E D E F A U L T C A L I B R A T I O N
1. Select Multivariable DP or pressure
2. Select Reset calibration method
3. Now verify the live reading against the flow computer reading
Summary of Contents for SFC332L
Page 15: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 10 Date 8 1 2019 Memory Jumper ...
Page 17: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 12 Date 8 1 2019 ...
Page 18: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 13 Date 8 1 2019 ...
Page 26: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 21 Date 8 1 2019 TURBINE SINE WAVE ...
Page 35: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 30 Date 8 1 2019 ...