INPUT/OUTPUT: Assigning and Ranging Inputs
Input/Output Assignment
We will now configure your SFC332L Flow Computer’s inputs and outputs. The flow computer allows the
user to configure the inputs and outputs. (I.e. Analog #1 is pressure for Meter #1). The flow computer will
not use the unassigned inputs.
How to assign a transmitter to an I/O point
1
Click “Configure Device”, configuration menu is prompted
2
On configuration menu, click “Input Assignment”
3
Enter assignments for DP, temperature, pressure, density and spare inputs.
4
Assignment (1-n)
. Assignments 1-4 are analog inputs attached
to terminal of the back panel. These inputs accept
4-20mA or 1-5
volts input and are suitable for temperature, pressure, density, or spare inputs. An assignment
5 is strictly RTD (temperature) input only for the meter, densitometer or spare. Assignment 7
indicates a density frequency input; it is assigned automatically once you choose live density
frequency input in the setup menu at density type Assignment 10 (module 1) is for
Rosemount multi-variable module only. DP, pressure, and temperature for the meter can be
assigned. When a frequency type primary element is hooked to the flow computer, the Multi
Variable pressure and temperature can be used and the DP becomes a spare input that could
be assigned for strainer differential.
Summary of Contents for SFC332L
Page 15: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 10 Date 8 1 2019 Memory Jumper ...
Page 17: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 12 Date 8 1 2019 ...
Page 18: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 13 Date 8 1 2019 ...
Page 26: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 21 Date 8 1 2019 TURBINE SINE WAVE ...
Page 35: ...Dynamic Flow Computers SFC332L Manual Quick Start 1 30 Date 8 1 2019 ...