![background image](http://html1.mh-extra.com/html/dmp-electronics/xr200/xr200_programming-manual_2513867023.webp)
XR200/XR2400F Programming Guide
Digital Monitoring Products
15
5.1
Remote Options
This section allows you to enter the information needed for Remote Command/
Remote Programming operation.
5.2
Remote Key
This option allows you to enter a code of up to eight digits for use in verifying the
authority of an alarm or service receiver to perform a remote command/
programming session. The Remote Link™ program must give the correct key to the
panel before being allowed any remote functions. All panels are shipped from the
factory with the key preset as blank.
To enter a remote key or change the current one, press a top row Select key and
enter any combination of up to eight digits. Press COMMAND. The current key is
never displayed.
5.3
Manufacturer Authorization
Select
YES
to allow DMP Technical Support technicians to access the panel during
system service or troubleshooting. This authorization automatically expires within
one hour.
DMP remote service is provided on a read only basis:
DMP technicians can look
at the system programming and make suggestions only. Alterations can only be
accomplished by the installing company's service personnel.
5.4
Armed Rings
Enter the number of rings the panel counts before answering the phone line when
all areas of the system are armed. Any number from 1 to 15 can be entered. If
zero is entered, the panel does not answer the phone when all areas of the system
are armed. The default Armed Rings for the XR200 is
0
(zero). The default
number of Armed Rings for the XR2400F is
10
.
5.5
Disarmed Rings
Enter the number of rings the panel counts before answering the phone line while
any areas of the system are disarmed. Any number from 1 to 15 can be entered.
If zero is entered, the panel does not answer the phone when any area of the
system is disarmed. The default number of Disarmed Rings for the XR200 is
0
(zero). The default number of Disarmed Rings for the XR2400F is
10
.
5.6
Alarm Receiver Authorization
Select
YES
to enable remote commands and programming to be accepted from the
alarm SCS-1 Receiver. The Remote Key option can also be required.
With
YES
selected, the panel requests the receiver key during its first
communication with the first SCS-1 receiver. The panel retains this
alarm
receiver key
in memory and allows remote commands to be accepted from the
alarm receiver. If an alarm occurs during a remote connect, the alarm report is
immediately sent to this receiver only.
When
NO
is selected, remote commands and programming are not accepted from
the alarm SCS-1 Receiver.
ALR RCVR
NO
YES
DISARM RINGS: 0
ARM RINGS: 0
MFG AUTH
NO
YES
RMT KEY:
REMOTE OPTIONS
5 - REMOTE OPTIONS