Digital Monitoring Products
XR200/XR2400F Programming Guide
20
8.1
Output Options
This function allows you to program the panel's Bell Output functions and certain
Relay Output options. Dry contact relays and voltage outputs are available using
the output harness on the panel. See the Installation Guide for more information.
8.2
Bell Cutoff Time
Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the
Bell Output is manually silenced or the area is disarmed, the cutoff time is reset.
Enter zero to provide continuous bell output. XR200 default setting is
15
minutes;
XR2400F is
5
minutes.
8.3
Automatic Bell Test
When
YES
is selected, the Bell Output is turned on for 2 seconds each time a
partition is completely armed from a keypad. This test is delayed until the
Closing Wait acknowledge is received (if selected). If the Closing Wait
acknowledge is not received within 90 seconds, the bell test will not occur. The
Bell Test only occurs when the areas are armed from a keypad. Arming performed
from an Arming zone or from Remote Link™ does not activate the Bell Test.
8.4
Bell Action
This section allows you to define the type of Bell Output for zone
alarms
.
(Trouble conditions do not activate the Bell Output.) Press COMMAND to display
the default Bell Output for each zone type. To change the output, press any
Select key and enter
S
to provide a Steady Bell Output,
P
for a Pulsed output.
T
for a Temporal Code 3 output, and
N
for no Bell Output.
8.4.1
Fire Bell Action
Defines Bell Action for Fire Type zones. The XR200 factory default is set at P. The
XR2400F factory default is set at S.
8.4.2
Burglary Bell Action
Defines Bell Action for Burglary Type zones and Exit Error output. The XR200
factory default is set at S. The XR2400F factory default is set at N.
8.4.3
Supervisory Bell Action
Defines Bell Action for Supervisory Type zones. The default is set at N.
8.4.4
Panic Bell Action
Defines Bell Action for Panic Type zones. The default is set at N.
8.4.5
Emergency Bell Action
Defines Bell Action for Emergency Type zones. The default is set at N.
8.4.6
Auxiliary 1 Bell Action
Defines Bell Action for Auxiliary 1 Type zones. The default is set at N.
8.4.7
Auxiliary 2 Bell Action
Defines Bell Action for Auxiliary 2 Type zones. The default is set at N.
8.5
Output Action
This option allows you to define the operation of the XR200 and XR2400F relay
outputs. The panel provides two Form C relays (1 and 2) and eight 12 VDC voltage
outputs (3 to 10) rated at 50mA each. You can expand the system to 200
additional relay outputs (numbered 100 to 299) using multiple 716 Output
Expander Modules and at least two expansion interface cards.
8.5.1
Cutoff Output
Outputs 1 to 8 can be entered here to turn off after a time specified in
CUTOFF
TIME
. To disable this option, press any Select key to clear the display then press
COMMAND. The Cutoff Output displays
NONE
when no outputs are selected.
8.5.2
Output Cutoff Time
If a Cutoff Output is assigned, you can enter a Cutoff Time of 1 to 99 minutes for
the output to remain on.
Enter zero for continuous output.
BELL ACTION . . . .
BELL CUTOFF: 15
OUTPUT OPTIONS
BELL TST
NO
YES
FIRE TYPE: P
BURGLARY TYPE: S
SUPRVSRY TYPE: N
PANIC TYPE: N
EMERGNCY TYPE: N
OUTPUT ACTION . . .
CO OUTS: - - - - -
AUXLRY 2 TYPE: N
AUXLRY I TYPE: N
CUTOFF TIME: 0
8 - OUTPUT OPTIONS