Digital Monitoring Products
XR200/XR2400F Programming Guide
14
4.1
Device Setup
This section allows you to define the physical configuration of the panel. Enter
the number of partitions in the system and the types of devices installed at each
address along with their assigned partition. You can install and address up to
eight
supervised
devices on the keypad data bus. Zones are available only from
addresses 1-8.
A description of each option follows:
4.2
Maximum Partitions
Maximum number of partitions you want in this system. You can choose from 1 to
4. To change the number displayed, press any Select key, enter the number of
partitions you want to enable, and press COMMAND.
Changing the number of partitions resets user codes:
Whenever you change the
number of partitions on the panel, all programmed user codes are cleared. The
only user code available after a partition change is the factory default of 99.
4.3
Device Type
This prompt allows you to specify that a device is installed at a particular address
on the keypad bus.
STANDARD
- The device is either a Security Command keypad, a 711, 714, or 715
Zone Expander, a 6155LX PIR, 5845LX Glassbreak Detector, or a 733 Wiegand
Interface Module.
FIRE
- The device is an Addressable Fire Alarm Control panel or a Model 630F
Remote Fire Command Center.
NONE
- No device is set for this address.
If you entered 2, 3, or 4 in section 4.2
MAX PARTITION
, the keypad displays the
PARTITION NO:
prompt. If there is only one partition programmed in section 4.2,
the keypad does not display the partition assignment prompt.
4.4
Partition Number
Enter the partition number where the current device being programmed is
assigned. For systems with more than one partition, press any top row Select key
then enter a 1, 2, 3, or 4. Press COMMAND to program the next device. The
keypad can have up to eight devices.
DEVICE 1:
STNDRD
DEVICE NO: -
DEVICE SETUP
STD FIRE NONE
Partitions
Enabled
Areas Available
User Codes
Available
XR200
1
1 to 8
1 to 200
2
Partition 1 - 1 to 8
Partition 2 - 1 to 4
Partition 1 - up to 100
Partition 2 - up to 100
3
Partition 1 - 1 to 8
Partition 2 - 1 to 4
Partition 3 - 1 to 4
Partition 1 - up to 50
Partition 2 - up to 50
Partition 3 - up to 50
4
Partition 1 - 1 to 8
Partition 2 - 1 to 4
Partition 3 - 1 to 4
Partition 4 - 1 to 4
Partition 1 - up to 50
Partition 2 - up to 50
Partition 3 - up to 50
Partition 4 - up to 50
MAX PARTITION: 1
PARTITION NO: 1
4 - DEVICE SETUP