XR200/XR2400F Programming Guide
Digital Monitoring Products
21
8.5.3
Communication Fail Output
Enter output number to turn on when any of the following conditions occur:
• a DD system fails to communicate on three successive dial attempts
• a MPX system does not communicate with the receiver for 150 seconds or if
the backup communication line transmits a report
To clear the output, disarm any area.
Enter zero to disable this output.
8.5.4
Fire Alarm Output
Enter output number to turn on when a fire type zone is placed in alarm. The
output is turned off using the Sensor Reset option while no additional fire type
zones are in alarm.
Enter zero to disable this output.
This output is not
compatible with Cutoff Outputs.
8.5.5
Fire Trouble Output
Enter output number to turn on when a fire type zone is placed in trouble or when
a supervisory type zone is placed in alarm or trouble. The output is turned off
when all fire and supervisory type zones are restored to normal.
Enter zero to
disable this output.
This output is not compatible with Cutoff Outputs.
8.5.6
Ambush Output
Enter output number to turn on when an Ambush code is entered at a keypad. The
output is turned off using the Sensor Reset option.
Enter zero to disable.
8.5.7
Entry Output
Enter output number to turn on at the start of the entry delay time. The output is
turned off when the area is disarmed or the entry delay time expires.
Enter zero
to disable this output.
8.5.8
Exit Output
Enter output number to turn on when an exit delay time starts in any area of the
system. The output is turned off when the area arms or when the arming has
been stopped. Enter zero to disable this output.
8.5.9
Ready Output
Enter output number to turn on when all disarmed burglary zones are in a normal
state. The output is turned off when any disarmed burglary type zone is in a bad
state.
Enter zero to disable.
This output is not compatible with Cutoff Outputs.
8.5.10
Phone Trouble Output
Enter output number to turn on when the phone line monitor in the DMP 893 or
893A Dual Phone Line Module detects a voltage below 3 VDC. The output is turned
off when phone voltage rises above 3 VDC.
Enter zero to disable this output.
8.5.11
Late To Close Output
Enter the output number to turn on at the expiration of a Closing schedule. The
output activates simultaneously with the
CLOSING TIME!
keypad display. The
output is turned off when the area is armed, the Closing is extended, or the
schedule is changed.
Enter zero to disable this output.
8.5.12
Device Fail Output
Enter output number to turn on when an addressed device fails to respond to
polling from the panel. A Missing Device report is also sent to the receiver. The
output is turned off when the device responds to polling or is removed from the
system.
Enter zero to disable this output and LX-Bus™ device fail reporting to
the receiver.
If any keypad addressed device is unsupervised, then this output
option cannot be used.
8.5.13
Sensor Reset Output
Enter an output number to turn on when a Sensor Reset is performed at a keypad.
The output turns off automatically 5 seconds later. This function can be used to
reset smoke detectors that are operated by an external power supply through a
Model 716 Output Expander Module.
Enter zero to disable this output.
FIRE TRB OUT: 0
AMBUSH OUT: 0
ENTRY OUT: 0
EXIT OUT: 0
READY OUT: 0
PH TRBL OUT: 0
LATE CLS OUT: 0
FIRE ALR OUT: 0
DVC FAIL OUT: 0
COM FAIL OUT: 0
SNSR RST OUT: 0
8 - OUTPUT OPTIONS