14.16
Cross Zone
Select
YES
to enable cross zoning for this zone. Cross zoning requires one or more
armed zones to fault within a programmed time before an alarm report is sent to
the receiver.
When a cross zoned zone trips, the bell action assigned to the zone activates. The
cross zone time specified in System Options begins to count down. If another
cross zoned zone in the same area faults, or if the first zone restores and faults
again before a Sensor Reset is done, the panel sends an alarm report.
If no other cross zoned zone in the same area trips before the cross zone time
expires, the panel sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types:
You cannot enable cross
zoning for Fire verify zones or for any Fire zones that have Retard Delay enabled.
14.17
Priority
Select
YES
to provide additional protection for the premises by requiring this zone
to be in a normal condition before its assigned area can be armed.
ZONE NUMBER
- Enter the zone number to program next. Follow the descriptions
of each programming prompt. If all zones are programmed, press the Back Arrow
key at the
ZONE NO: –
display to continue.
Note
:
If you programmed any wireless zones, press the Back Arrow key for the
following wireless programming.
The next three prompts are for use with the
FA400 Remote Wireless Receiver.
14.17.1
Program Transmitter
Select YES
to program wireless transmitters. Select
NO
to return to
Zone
Information
.
14.17.2
Connect Transmitter
Connect the transmitter, whose zone number is displayed, to the Programming
Connector on the 472 Inovonics 900MHz Card using the 620 Programming Cable.
RESET THE TRANSMITTER
. The keypad display prompts you for transmitters
starting from the lowest zone number to the highest.
At the
CONNECT XMTR:
prompt, you can also press a Select key and enter in any
wireless zone number (100 to 299 or 000 for the C100 and FA100 transmitters).
After programming all transmitters, press the COMMAND key.
14.17.3
Connect Command Transmitter
Connect the FA100 or FA113 you want assigned to the partition shown (P1 =
Partition 1) to the 472 Card. Press the Alert button on the transmitter to initiate
programming. Repeat the programming for each partition. To use the Alert
button on the transmitter as a panic, program
AMBUSH
as
YES
in System Reports.
Additional Zone Programming
The remaining Zone Information you need to specify varies with the different Zone
Types. Below is a list of the remaining information needed:
If Zone Type
Remaining Information
Exit
Prewarn addresses/Entry Delay
Fire, Supervisory,
Retard and Presignal addresses
Auxiliary 1 and 2
CRS ZONE
NO
YES
CONNECT FA100 P 1
CONNECT XMTR: ***
PRG XMTR? NO YES
PRIORITY
NO
YES
ZONE NO: –