Digital Monitoring Products
XR200/XR2400F Programming Guide
18
7.1
System Options
This section allows you to select system wide parameters used in the operation of
the system. A description of each System Option follows:
7.2
Closing Wait
When
YES
, the keypad displays
ONE MOMENT...
while the system waits for an
acknowledge from the receiver before arming the selected area(s) and performing
a Bell Test (if selected). The acknowledge must be received within 90 seconds.
Exit delays begin after this period. Opening/Closing reports must be
YES
to
enable Closing Wait.
7.3
Entry Delay 1
Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay
1. When an armed Exit type zone is faulted, the keypad prewarn tone begins
sounding and
ENTER CODE:-
displays on all keypads programmed to prewarn for
that zone. The area must be disarmed before the delay expires or an alarm report
is sent to the receiver. All zones in that area are delayed along with the Exit
zone. Entry Delay times can be from 1 to 250 seconds.
Repeat the above for each entry delay being used in the system.
7.4
Cross Zone Time
Enter the time allowed between zone faults. When zones are cross zoned, a
second cross zoned zone in the same partition must fault within this time in order
for an alarm report from the first zone to be sent to the receiver. If the cross
zone time expires without the second zone faulting, only a zone fault from the
first zone is reported. Cross zone time can be from 4 to 250 seconds. Entering
zero disables this function. See the Appendix.
7.5
Zone Retard Delay
Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, and Auxiliary 2
type zones. The retard delay only functions when the zone is shorted. The zone
must remain shorted for the entire length of the Retard Delay before being
recognized by the panel. The Zone Retard Delay can be from 1 to 250 seconds.
Entering a zero disables this function.
7.6
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off
for the length of the programmed delay time, an AC power failure report is sent to
the receiver. The delay time can be from 1 to 9 hours. Entering a zero sends the
AC power failure report after a 15 second delay. XR200 default setting is
1
;
XR2400F is
6
.
7.7
Swinger Bypass Trips
Enter the number of times a zone can go into an alarm or trouble condition within
one hour before being automatically bypassed. You can select from 1 to 7 trips.
Bypassed zones are automatically reset when the area they are assigned to is
disarmed. All 24 hour zones are reset when any area of the system is disarmed.
Entering a zero disables this function.
How it works
The panel's hour timer starts at 59 minutes past the hour. If the hour timer
expires before the trip counter is exceeded, the trip counter returns to zero. If
the trip counter is exceeded before the hour expires, the zone is automatically
bypassed by the panel. A report of the automatic bypass is sent to the receiver if
Bypass Reports has been selected as
YES
.
7.8
Reset Swinger Bypass
When
YES
is selected, an automatically bypassed zone is reset if it remains in a
normal condition for one complete hour after being bypassed. A report of the
automatic reset is sent to the receiver if Bypass Reports has been selected as
YES
.
SYSTEM OPTIONS
RST SBYP NO
YES
CLS WAIT
NO
YES
CRS ZONE TM: 4
RETARD DLY: 10
ENTRY DLY 1: 30
ENTRY DLY 2: 60
ENTRY DLY 3: 90
ENTRY DLY 4: 120
PWR FAIL HRS: 1
SWGRBYPS TRIPS: 3
7 - SYSTEM OPTIONS