Digital Monitoring Products
XR200/XR2400F Programming Guide
32
14.5
Fire Bell Output
This output (1 to 10, 100 to 299) is turned on any time a Fire, Fire Verify, or
Supervisory zone is placed in alarm. The output is turned off by any the following
actions:
• When the User Menu Alarm Silence function is performed.
• When a valid user code is entered to silence the bell.
• When the Silence key is pressed on the XR2400F or the 630F Remote Fire
Command Center.
• Using the Outputs On/Off function in the User Menu.
• The expiration of the Bell Cutoff time.
NOTE:
When programming XR2400F fire zones, assign output number 1 to Fire
Bell Output to turn on NAC 1 and output number 2 to turn on NAC 2. This
causes a NAC to turn on when a fire zone is in alarm.
14.6
Partition Number
Enter the partition number where this zone is being assigned.
14.6.1
Area Number
For an Area system, enter the area number where this zone is being assigned.
14.6.2
Area Assignment
For an All/Perimeter system, choose INT. (interior) or PERIM (perimeter). For a
Home/Away system, choose INT (interior), BDRM (bedroom), or PERIM (perimeter).
Press the Select key under your selection.
14.6.3
Arming Zone Area Assignment
If the zone has been programmed as an Arming Type (AR), the only information to
enter is the areas the zone controls. If the Arming zone is in a partition
programmed as an Area system, enter the area numbers to be armed and
disarmed.
If the partition is in an All/Perimeter system, select either
PERIM
(perimeter) or
ALL
.
If the partition is in a Home/Away system, select
HOME
(for the perimeter area),
SLEEP
(for perimeter and interior areas), or
AWAY
(for perimeter, interior, and
bedrooms areas).
If the Arming zone is opened while any areas it controls are armed, a burglary
alarm occurs. If the zone is restored to normal, the areas cannot be disarmed
using the Arming zone until at least one other area within the same partition is
disarmed remotely, from a keypad, or from another Arming zone.
If the Arming zone is opened while all areas assigned to it are disarmed, a burglary
trouble occurs. If the zone restores to normal, a burglary restoral occurs.
To visually indicate the armed state of the area(s), you can assign an Armed
Output to individual areas and use remote LEDs at the keyswitch. The LED turns
on or off to indicate to the user the armed state of the area(s).
If any bad zones are present when the Arming zone is shorted, the LED delays
lighting for five seconds. If during the five second delay the Arming zone is
shorted again, no arming takes place. To force arm bad zones, the Any Bypass
option must be set to
YES
. A priority zone cannot be force armed.
FIRE BEL OUT: 0
PARTITION NO: 1
AREA NO: -
AREA : PERIMETER
AREAS:1 _ _ _ _ _ _ _
PERIM ALL
HOME SLEEP AWAY
14 - ZONE INFORMATION