7 - 5 8
Modulon DPH Series
Item
Sub Item
Description
INPUT
CONTACT
Input Contact 1
1. Set the input contact as Normally Open (NO)/ Normally
Closed (NC).
2. Set the title for the input contact, 16
characters
at most.
3. Set the Event Type as None/ Information/ Warning/ Alarm.
Input Contact 2
Input Contact 3
Input Contact 4
Not only does the
EMS
screen show status of the input contacts (please refer to
7.9.7
EMS
), but the
Warning
screen,
Historical Event
screen, UPS tri-color LED indicator and
buzzer also response to the status of the input contacts.
NOTE:
For the location of the UPS tri-color LED indicator and buzzer, please refer
to
2.8 Tri-color LED Indicator & Buzzer
.
Event Type
of Input
Contact
EMS
DI1~DI4
(LCD)
Tri-color
LED
Indicator
Buzzer
Warning
(LCD)
Historical
Event
(LCD)
None
Green
Green
No Sound
No
No
Information
Green
Green
No Sound
No
Yes
Warning
Yellow
Yellow
Short Beep
Yes
Yes
Alarm
Red
Red
Long Beep
Yes
Yes
All the above settings are related to the items shown on the
EMS
screen in the
MEASUREMENT
ĺ
EMS
. Please refer to
7.9.7 EMS
.
7.10.11 BMS Setting
Path:
SETUP
ĺ%066HWWLQJ
After entering the
BMS SETTING*
1
VFUHHQVKRZQLQWKH¿JXUHEHORZ\RXFDQYLHZWKH
Alarm Threshold Values (High & Low)*
2
of
Cell Voltage
,
String Voltage
and
Ambient
Temperature*
3
of the
Main Module
and each
Ext #n Module
of the optional battery
management system (BMS).
You can also set up the following items. These settings must be carried out by qualified
service personnel. Please contact Delta customer service for assistance.
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......