5 - 2 8
Modulon DPH Series
2SWLRQ,QVWDOODWLRQRIDSROH'&FLUFXLWEUHDNHUYROWDJHSHUSROH9GF
-
N
+
UPS
External
Battery
Cabinet
3-Pole DC Circuit Breaker
-
N
+
(Figure 5-24: Installation of a 3-Pole DC Circuit Breaker)
y
To save on your costs and installation space, the parallel UPSs (at maximum 8 units)
can share their connected external battery cabinet(s). For relevant information, please
refer to
3.4 Common Battery (Only for Parallel UPSs Connecting to the Same Ex-
ternal Battery Cabinet(s))
.
WARNING:
%HIRUHSHUIRUPLQJEDWWHU\EDWWHU\FDELQHWUHSODFHPHQWSOHDVHWXUQRႇHDFK
external battery cabinet’s breaker (Q5) to completely disconnect the battery
power from the UPS.
2. A battery can present a risk of electric shock and high short-circuit current.
Servicing of batteries and battery cabinets must be performed or supervised
E\TXDOL¿HGVHUYLFHSHUVRQQHONQRZOHGJHDEOHLQEDWWHULHVEDWWHU\FDELQHWV
and the required precautions. Keep unauthorized personnel away from
batteries and battery cabinets.
y
External Battery Cabinet Alarm
When any external battery cabinet connected to the UPS has the following problems,
the UPS system will sound an alarm. Please see the table below.
No.
External Battery Cabinet Status
Alarm
1
Battery Abnormal - Reversed
Sounds for 50ms every second.
2
Battery Ground Fault
Sounds for 50ms every second.
3
Battery Over Temperature
Sounds for 50ms every second.
4
Battery Under Temperature
Sounds for 50ms every second.
5
%DWWHU\%UHDNHU2ႇ
Sounds for 50ms every 3 seconds.
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......