3. Check if the wiring is correct. Ensure that the AC power’s voltage, frequency, phase
sequence and battery type meet the UPS’s requirements.
4. Check if all power modules are properly installed and every power module’s switch
is in the upper position (
). Please refer to
5.8 Power Module (Optional)
for more
information.
y
3UH7XUQRႇ:DUQLQJVIRU6LQJOH8QLW
If you perform turn-off procedures for single unit, all power will be completely cut off.
Please make sure the critical loads connected to the UPS have already been safely shut
GRZQEHIRUH\RXSHUIRUPWKHWXUQRႇSURFHGXUHV
Parallel Units
y
Pre Start-up Warnings for Parallel Units
1. You can parallel at maximum eight UPS units.
2. For parallel units, ensure that each parallel cable (provided) is connected well.
3. Make sure that all the breakers, including every external battery cabinet’s breaker
(Q5), are turned to the
OFF
position.
4. Make sure that each parallel UPS’s voltage difference between the Neutral (N) and
Ground (
) is < 3V.
5. Check if the wiring is correct. Ensure that the AC power’s voltage, frequency, phase
sequence and battery type meet the UPS’s requirements.
6. Check if all power modules are properly installed and every power module’s switch
is in the upper position (
). Please refer to
5.8 Power Module (Optional)
for more
information.
7. For parallel units, ensure that every operation procedure is synchronized to all
parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOOSDUDOOHO
ones, please contact service personnel.
y
3UH7XUQRႇ:DUQLQJVIRU3DUDOOHO8QLWV
,I\RXZDQWWRWXUQRႇRQHRIWKHSDUDOOHO836VSOHDVHFKHFNZKHWKHUWKHUHPDLQLQJ
parallel units’ total capacity exceeds the total critical loads. If the remaining parallel
units’ total capacity is less than the total critical loads, all parallel units will shut down
due to overload.
2. If you perform turn-off procedures for all parallel UPSs, all power will be completely
FXWRႇ3OHDVHPDNHVXUHWKDWWKHFULWLFDOORDGVFRQQHFWHGWRWKHSDUDOOHO836VKDYH
DOUHDG\EHHQVDIHO\VKXWGRZQEHIRUH\RXSHUIRUPWKHWXUQRႇSURFHGXUHV
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......