3 - 1 8
Modulon DPH Series
3.2.4 Manual Bypass Mode_ Dual Input_ Single Unit
WARNING:
1. In Manual Bypass mode, make sure that all of the breakers (except the Manual
Bypass Breaker (Q3)) are in the
OFF
position before working on the UPS’s
internal circuits. This avoids electric shock.
$IWHUWKHSRZHULQVLGHWKH836LVFRPSOHWHO\FXWRႇWKHUHLVQRKLJKYROWDJH
inside the UPS and maintenance can be performed safely. However, to avoid
electric shock, please do not touch the following parts: AC Input terminal block,
Bypass Input terminal block, UPS Output terminal block, Battery Input terminal
block, grounding terminals (see
Figure 5-8
~
Figure 5-11
for the location of
these terminal blocks and terminals) and any copper bars connected to the
Manual Bypass Breaker (Q3), as they may carry high voltage.
'XULQJ0DQXDO%\SDVVPRGHWKH836¶VLQSXWSRZHULVFRPSOHWHO\FXWRႇDQG
the connected critical loads are not protected.
When the UPS needs maintenance, you can manually switch the UPS to Manual Bypass
mode. To let the UPS run in Manual Bypass mode, please follow the procedures below:
1
&RQ¿UPWKDWWKHE\SDVV$&VRXUFHDQGWKH676PRGXOHDUHQRUPDO
2
Tap the LCD’s ON/ OFF Button (
) and the '
POWER OFF?
' screen will pop up to
DVNLI\RXZDQWWRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFW
'
YES
'.
3
Turn
ON
the Manual Bypass Breaker (Q3).
4
Turn
OFF
the Bypass Breaker (Q2).
5
Turn
OFF
the Input Breaker (Q1) and Output Breaker (Q4).
6
Turn
OFF
each external battery cabinet’s breaker (Q5).
,Q0DQXDO%\SDVVPRGHDOOSRZHULQVLGHWKH836LVFRPSOHWHO\FXWRႇDQGPDLQWHQDQFH
personnel can perform maintenance safely. Please see
Figure 3-18
for Manual Bypass
PRGHGLDJUDP'XULQJ0DQXDO%\SDVVPRGHWKH836¶VWULFRORU/('DQG/&'DUHERWKRႇ
Summary of Contents for Modulon DPH series
Page 26: ......
Page 58: ......
Page 168: ......
Page 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 240: ......
Page 241: ...9 1 9 Maintenance Maintenance 9...
Page 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 246: ......
Page 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 250: ......