227
4) Send a voltage signal (approximately 8 V) to AI.
5) Measure AI voltage and save it to PF.03.
6) View the displayed value of b0.21 and save the value to
PF.04.
PF.04
CI measured voltage 1
Setting Range:
0.500 V
~
4.000 V
Factory-corrected
PF.05
CI displayed voltage 1
Setting Range:
0.500 V
~
4.000 V
Factory-corrected
PF.06
CI measured voltage 2
Setting Range:
6.000V
~
9.999V
Factory-corrected
PF.07
CI displayed voltage 2
Setting Range:
6.000V
~
9.999V
Factory-corrected
These parameter corrected method is the same with PF.00 to
PF.03, view the displayed value of b0.22.
PF.12
AO1 target voltage 1
Setting Range:
0.500 V
~
4.000 V
Factory-corrected
PF.13
AO1 measured voltage 1
Setting Range:
0.500 V
~
4.000 V
Factory-corrected
PF.14
AO1 target voltage 2
Setting Range:
6.000V
~
9.999V
Factory-corrected
PF.15
AO1 measured voltage 2
Setting Range:
6.000V
~
9.999V
Factory-corrected
These parameters are used to correct the AO