176
34
:
Zero current state
:
Refer to the descriptions of P2.32 and P2.33.
35
:
Module temperature reached
If the heat-sink temperature of the inverter module (P7.06) reaches the set module
temperature threshold (P2.45), the terminal becomes ON.
36
:
Software current limit exceeded
:
Refer to the descriptions of P2.32 and P2.33
37
:
Frequency lower limit reached (having output at stop)
If the running frequency reaches the lower limit, the terminal becomes ON. In the stop state,
the signal becomes OFF.
38
:
Fault output
:
If a fault occurs on the AC drive and the AC drive stop, the terminal
becomes ON.
39
:
Motor overheat warning
If the motor temperature (b0.34) reaches the temperature set in PA.54 (Motor overheat
warning threshold), the terminal becomes ON.
40
:
Current running time reached
:
If the current running time of AC drive exceeds the
value of P2.51, the terminal becomes ON.
41
:
Fault output
When the AC drive stops due to a fault, the terminal becomes ON.
Mark
:
No output when under-voltage
P4.06
FMP function selection
Setting Range
:
0
~
16
0
P4.07
AO1 function selection
Setting Range
:
0
~
16
0
P4.08
AO2 function selection
Setting Range
:
0
~
16
1