P4.01
FMR function (open-collector
output terminal)
Setting Range
:
0
~
41
0
P4.02
Relay function
(
T/A-T/B-T/C
)
Setting Range
:
0
~
41
2
P4.03
Extension card relay
function
(
R/A-R/B-R/C
)
Setting Range
:
0
~
41
0
P4.04
DO1 function selection (open-
collector output terminal)
Setting Range
:
0
~
41
1
P4.05
Extension card DO2 function
Setting Range
:
0
~
41
4
These five parameters are used to select the functions of the five digital output terminals.
T/A-T/B-T/C and P/A-P/B-P/C are respectively the relays on the control board and the
extension card.
The functions of the output terminals are described in the following table.
Table 6-3 Functions of output terminals
Value
Function
Value
Function
0
No output
1
AC drive running
2
Fault output (stop)
3
Frequency-level detection FDT1 output
4
Frequency reached
5
Zero-speed running(no output at stop)
6
Motor overload pre-warning
7
AC drive overload pre-warning
8
Set count value reached
9
Designated count reached
10
Length reached
11
PLC cycle complete
12
Current running time reached
13
Frequency limited
14
Reserved
15
Ready for RUN
16
VI larger than AI
17
Frequency upper limit reached
18
Frequency lower limit reached
(no output at stop)
19
Under-voltage state output
20
Communication setting
21
Reserved