When the AC drive is in communication with the master, the host
computer writes data -100.00% to 100.00% by the
communication address 0x1000, where 100.0% corresponds to
the value of P9.11.
P9.14
Excitation adjustment proportional gain
Setting Range: 0
~
20000
2000
P9.15
Excitation adjustment integral gain
Setting Range: 0
~
20000
2000
P9.16
Torque adjustment proportional gain
Setting Range: 0
~
20000
2000
P9.17
Torque adjustment integral gain
Setting Range: 0
~
20000
2000
These are current loop PI parameters for vector control. These parameters are
automatically obtained through "Asynchronous motor complete auto-tuning" or
"Synchronous motor no-load auto-tuning", and need not be modified.
The dimension of the current loop integral regulator is integral gain rather than integral time.
Note that too large current loop PI gain may lead to oscillation of
the entire control loop. Therefore, when current oscillation or
torque fluctuation is great, manually decrease the proportional
gain or integral gain here.
P9.24
Torque setting source in torque control
0
~
5
0
P9.26
Torque digital setting in torque control
0.0%
~
200.0%
150.0%
For details of these parameters setting, refer to
P9.10
(
P9.24
)
and P9.11
(
P9.26
)
.