![degdrive DGI900 User Manual Download Page 186](http://html.mh-extra.com/html/degdrive/dgi900/dgi900_user-manual_2464871186.webp)
186
Figure 6-26 Principle block diagram of PID control
P6.00
PID setting source
Setting Range
:
0
~
5
0
P6.01
PID digital setting
Setting Range
:
0.0%
~
100.0%
50%
0
:
P6.01 setting
;
1
~
2: VI
、
CI
;
4
:
Pulse setting
(
X5/HDI
)
5
:
Communication setting
P6.00 is used to select the channel of target process PID setting.
The PID setting is a relative value and ranges from 0.0% to
100.0%. The PID feedback is also a relative value. The purpose
of PID control is to make the PID setting and PID feedback equal.
P6.02
PID feedback source
Setting Range
:
0
~
8
0
0
~
1: VI
、
CI
;
3
:
VI-CI
;
4
:
Pulse setting
(
X5/HDI
);
5
:
Communication setting
;
6
:
VI
;
7
:
MAX(|VI|, |CI |)
;
7
:
MIN(|VI|, |CI |)
This parameter is used to select the feedback signal channel of
process PID. The PID feedback is a relative value and ranges
from 0.0% to 100.
P6.03
PID action direction
Setting Range
:
0.00s
Summary of Contents for DGI900
Page 1: ...User Manual DGI900 ...